beautypg.com

Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 106

background image

14.1

95-8533

5-4

10. The calibration is complete. (The calibrate LED

turns off.)

Note

If the calibration procedure is not completed
within 12 minutes, calibration will be aborted and
the detector will revert back to the previous
calibration values. the red LeD will flash and the
calibration will be logged as aborted.

Initial Installation and Sensor Replacement —
Combustible Gas (CGS Sensor)

Note

When replacing a sensor, compare part numbers to
be sure that the correct replacement sensor is used.

wARNING!

the hazardous area must be de-classified prior
to removing a junction box cover with power
applied.

1. Remove the cover from the DCUEX enclosure.

2. Press the Sensor Replacement Switch on the

communication module for approxImately 1

second. (The calibrate LED on the communication

module flashes, indicating that it is ready for the

zero input.)

Note

Pressing the sensor replacement switch
prevents the communication module from
generating a fault signal when the input drops to
zero due to sensor removal. the calibration will
not be aborted if the calibration procedure is not
completed within 12 minutes.

3. Move the Calibration Switch to the “calibrate”

position.

4. Replace the sensor.

5. Connect a volt meter to the test points on the

transmitter board. Connect the “+” lead to TP1

(red). Connect the “–” lead to TP2 (black).

6. Wait at least 5 minutes for the sensor output to

stabilize, then adjust R2 for a reading of 0.40 vdc

(4 ma) on the meter.

Note

Do not make adjustments to R1 when calibrating
the sensor.

7. Move the Calibrate Switch to the “normal”

position.

8. Activate the reed switch for 4 seconds. (The red

LED flashes for 3 seconds while the switch is

activated.) The communication module records

the uncalibrated value in position one of the

calibration log and calibrates the zero value. The

calibrate LED goes on steady.

9. Move the Calibration Switch to the “calibrate”

position.

10. Apply the calibration gas and wait for the output

to stabilize.

11. With 50% LFL calibration gas applied to sensor,

adjust R3 for a reading of 1.2 vdc (12 ma) on the

volt meter.

12. Move the Calibrate Switch to the “normal”

position. (The red LED flashes.)

13. Activate the reed switch. The red LED flashes for

3 seconds while the switch is activated.

14. The communication module records the

uncalibrated value in the first register of the

calibration log and calibrates the span value. The

calibrate LED stays on steady.

15. Remove the calibration gas and replace the DCU

enclosure cover.

16. The communication module waits until the analog

value drops below 4% full scale. The calibration

is complete. (The calibrate LED turns off.)

Note

Pressing the Sensor Replacement Switch aborts
the current calibration.

Sensor Replacement — Toxic Gas

Note

When replacing a sensor, compare part numbers
to be sure the correct replacement sensor is
being used.

wARNING!

the hazardous area must be de-classified prior
to removing a junction box cover with power
applied.

1. Remove the cover from the DCU enclosure.

2. Press the Sensor Replacement Switch on the

communication module for approximately 1

second. (The calibrate LED flashes,

indicating it is ready for the zero input.)