14.1

95-8533

Two-Wire Smoke Detectors

The EDIO supports 2-wire devices from Kidde-Fenwal

and Apollo. Figure 3-31 shows the wiring for Apollo

detectors connected to EDIO Channel 1 through

terminals 1 and 2.

Figure 3-32 shows the typical wiring for Kidde-Fenwal

detectors connected to the EDIO through Channel 1

using terminals 1 and 2.

The EDIO supports either brand of detection products,

however, mixing brands is not supported on either a

single channel or module.

IMPORTANT

No more than 15 devices can be connected per
channel.

Unsupervised Output

Connect external system wiring to the appropriate

terminals on the terminal block. See Figure 3-33.

No connection should be made to “+ Supply”

terminal.

IN

OUT

UNUSED

OUT

OUT

IN

IN

A2283

1

-R

L1

L2

L1

L1

-R

L1

L2

L1

-R

L1

L2

2

3

+ SUPPLY A

IN–/OUT+ B

COMMON C

EOL

RESISTOR

5 K

A2284

1

2

3

UNUSED

3

6

7

1

2

3

6

7

1

2

3

6

7

1

2

+ SUPPLY A

IN–/OUT+ B

COMMON C

EOL

RESISTOR

5 K

Figure 3-31—Apollo 2-Wire Devices

Figure 3-32—Kidde-Fenwal 2-Wire Devices

+ SUPPLY A

IN– / OUT+ B

COMMON C

1

2

3

NOTE: SHUNT/FLYBACK DIODES DO NOT NEED

TO BE INSTALLED ON THE FIELD DEVICE.

CIRCUIT PROTECTION IS PROVIDED

WITHIN THE EDIO MODULE.

A2321

Figure 3-33—Unsupervised Output Configuration