Section 4 - operation, System controller, Pushbuttons – Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual
Page 78: Tronics
14.1
95-8533
4-1
Section 4
Operation
SYSTEM CONTROLLER
PUSHBUTTONS
The Controller has seven pushbuttons (located on the
front panel) for user interface. These pushbuttons
allow the operator to interact with the Controller to
respond to alarms and system status conditions,
access system status reports, and configure Controller
time and date settings.
The following paragraphs describe the function of
each pushbutton. Refer to Figure 4-1 for Controller
pushbutton locations.
Cancel
cancels the selected command, and returns
the menu to the last option list displayed.
Enter
chooses the menu item selected, and advances
the menu to the next options list. (See “Controller
Menu Options“ in this section for additional
information.)
Note
Pressing enter while alarms are actively scrolling
returns the display to the Main Menu.
Next
allows the operator to scroll through options
listed within each menu. Each time the NEXT
pushbutton is pushed, the current options list indexes
up one list item. (See “Controller Menu Options” in
this section for additional information)
Previous
allows the operator to scroll through options
listed within each menu. Each time the PREVIOUS
pushbutton is pushed, the current options list indexes
down one list item. (See “Controller Menu Options” in
this section for additional information)
Reset
resets all controller latched outputs that are no
longer active.
Acknowledge
silences the internal beeper.
Silence
turns on the Silence LED and sets Silence
status in user logic.
Cancel
Enter
Next
Previous
Reset
Acknowledge Silence
EAGLE QUANTUM PREMIER
Safety System Controller
Fire Alarm
Inhibit
Power
Supr
High Gas
Trouble
Cntrl Flt
Lon Fault
Low Gas
Ack
Silence
Out Inhibit
Eagle Quantum Premier
Time & Date
Cancel
Enter
Next
Previous
Reset
Acknowledge Silence
DET
-
TRONICS
®
Figure 4-1—EQP Controller Pushbutton Locations