Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 29

background image

14.1

3-10

95-8533

IMPORTANT!

Det-Tronics recommends the use of shielded
cable (required by ATEX) to prevent external
electromagnetic interference from affecting field
devices.

IMPORTANT!

Be sure that the selected cable meets the
specifications. The use of other cable types can
degrade system operation. If necessary, consult
factory for further suggested cable types.

1. Remove the cover from the Network Extender

enclosure.

2. Connect 24 vdc power lead wires and

communication network cable to the terminal

block. (See Figure 3-2 for terminal location and

Figure 3-3 for terminal identification).

See Table 3-8 to determine maximum wiring

length.

COM 1 -

Communication network connections:

Connect to COM 2 terminals of the next

device on the loop, A to A and B to B.

COM 2 -

Communication network connections:

Connect to COM 1 terminals of the

previous device on the loop, A to A and

B to B.

24 VDC -

Connect the "+" terminal to the positive

side of the 24 vdc power source. (Both

"+" terminals are connected internally.)

Connect the "–" terminal to the negative

side of the 24 vdc power source. (Both

"–" terminals are connected internally.)

3. Connect shields to the designated "shield"

terminals. The two shield terminals are connected

internally to ensure shield continuity.

CAUTION!

Do not ground either shield at the network
extender enclosure. Insulate the shields to
prevent shorting to the device housing or to any
other conductor.

4. Check ALL wiring to ensure that proper

connections have been made.

5. Inspect the junction box O-ring to be sure that it is

in good condition.

6. Lubricate the O-ring and the threads of the

junction box cover with a thin coat of grease to

ease installation and ensure a watertight

enclosure.

NOTE

The recommended lubricant is a silicone free
grease, available from Det-Tronics.

7. Place the cover on the enclosure. Tighten only

until snug. Do not over tighten.

TERMINAL NO. 1

1

12

A2021

Figure 3-2—Network Extender Wiring Terminal Location

Table 3-8—Maximum Wiring Length from Nominal 24 vdc

Power Source to Network Extender (Maximum wire lengths are

based upon the cable’s physical and electrical characteristics.)

Wire Size

Maximum Wiring Distance

Feet Meters

18 AWG (1.0 mm2)* 2200

650

16 AWG (1.5 mm2)* 3500

750

14 AWG (2.5 mm2)* 5600

1700

* Approximate Metric Equivalent.