Channels 4 and 5, Terminals 10 to 15
ZONE-1 and ZONE-2 Inputs
The IPM supports 2-wire devices from Kidde-Fenwal

and Apollo. Figure 3-55 shows the wiring for Apollo

detectors connected to IPM Channel 4 through

terminals 10 and 11.
Figure 3-56 shows the typical wiring for Kidde-Fenwal

detectors connected to the IPM through Channel 5

using terminals 13 and 14.
IPM Channels 4 and 5, labeled “Zone-1” and “Zone-2”

on the modules wiring legend, support either brand of

detection products however mixing brands is not

supported on either a single channel or module.
Notes: 1. Contact devices such as Fenwal heat

detectors may be used on ZONE 1 and 2

inputs as NFPA Class B circuit if supervision

is selected.

2.

The initiating device circuit(s) for use with the

deluge and pre-action system configuration must

be wired within 20 feet and in conduit from the

IPM.

Channel 6, Terminals 16 to 18
Unsupervised Output
Connect external system wiring to the appropriate

terminals on the terminal block. See Figure 3-57. No

connection should be made to “+ Supply” terminal.

IN

OUT

UNUSED

OUT

OUT

IN

IN

A2241

10

-R

L1

L2

L1

L1

-R

L1

L2

L1

-R

L1

L2

11

12

+ SUPPLY A

IN–/OUT+ B

COMMON C

Figure 3-55—CH-4 and/or 5: Apollo 2-wire devices

A2242

13

14

15 UNUSED

3

6

7

1

2

3

6

7

1

2

3

6

7

1

2

+ SUPPLY A

IN–/OUT+ B

COMMON C

Figure 3-56—CH-4 and/or 5: Kidde-Fenwal 2-wire devices

+ SUPPLY A

IN– / OUT+ B

COMMON C

16

17

18

B2093

NOTE: SHUNT/FLYBACK DIODES DO NOT NEED

TO BE INSTALLED ON THE FIELD DEVICE.

CIRCUIT PROTECTION IS PROVIDED

WITHIN THE IPM.

BELL, HORN,
STROBE, ETC.

Figure 3-57—CH-6: Unsupervised Output Configuration