beautypg.com

Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 75

background image

14.1

3-56

95-8533

Terminals 1 to 4 —

Output terminals

Connect the first output

device between terminals 1

and 2, and the second

between terminals 3 and 4.

NOTE

Polarity shown in Figure 3-69 is for monitoring
condition; polarity is reversed when activated.

Each circuit must have a 10

kohm EOL resistor.

Terminals 5 to 10 — LON signaling circuit

terminals

Be sure to observe polarity

when wiring the LON.

5 — “A” side of signaling

circuit for COM 2

6 — “B” side of signaling

circuit for COM 2

7 and 8 —

s h i e l d

connections

9 — “A” side of signaling

circuit for COM 1

10 — “B” side of signaling

circuit for COM 1

Terminals 11 to 14 — 24 vdc power input

Connect the module power

supply to terminals 12 and

13. If an auxiliary output

supply is used for powering

signaling devices, it should

be connected to terminals 11

and 14.

Jumpers
Terminals 13 and 14 are connected by jumper JP2

and terminals 11 and 12 are connected by jumper

JP1. These two jumpers (JP1 and JP2) must be cut if

an auxiliary output power supply is being used. (See

Figure 3-70) for jumper locations.

Address Setting
Set device network address. (See “Setting Device

Network Addresses” in this section.)

9 10

7 8

5 6

3 4

1 2

1314

1112

JP1
JP2

B1903

Figure 3-70—Signal Audible Module Wiring Terminals and Jumpers

1

2

3

4

5

6

7

8

9

10

14

13

12

11

+

+

24 VDC

+

+

A

B

A

B

OUTPUT 1

*

OUTPUT 2

*

COM 2

COM SHIELD

COM 1

*

POLARITY SHOWN IS FOR MONITORING CONDITION,

POLARITY IS REVERSED WHEN ACTIVATED.

NOTE:

TERMINALS 12 AND 13 ARE FOR MODULE POWER SUPPLY.

TERMINALS 11 AND 14 ARE FOR AUXILIARY OUTPUT POWER SUPPLY.

JUMPERS JP1 AND JP2 MUST BE REMOVED IF AN AUXILIARY POWER SUPPLY IS USED.

B1901

10K EOL

10K EOL

Figure 3-69—Wiring Configuration for Signal Audible Module