86

PULSAlarm

Symptom

Probable Cause

Possible Solution

Not

Input wired incorrectly.

Check wiring.

Responding to
PULSAlarm

Input not configured properly.

Review Section 7-General Operation: Menu,
Leak Detection Failure Set-up
.

Input

Powered contact used.

Remove and replace with dry contact. If no
change, contact Technical Services.

LEVEL

Symptom

Probable Cause

Possible Solution

Input wired incorrectly.

Check wiring.

Not
Responding to
Level Input

Input not configured properly.

Review Section 7-General Operation: Menu,
Level Input Set-up
.

Powered contact used.

Remove and replace with dry contact. If no
change, contact Technical Services.

ANALOG OUTPUT

Symptom

Probable Cause

Possible Solution

Output wired incorrectly.

Check wiring.

Output fuse(s) blown.

Replace F2 & F3 w/

50mA@250VAC

.

No Analog
(mA) Signal
Present.

Not tracking

Output not calibrated properly.

Review Section 7-General Operation:
Calibration
.

ALARM RELAY OUTPUT

Symptom

Probable Cause

Possible Solution

No Output

Output wired incorrectly.

Check wiring.

External Device not powering output.

Refer to Section 8 – Diagram 1 – DLC Wiring
Diagram
. External device must supply
voltage to dry contact.

Alarm Options not set.

Review Section 7-General Operation: Leak
Detection/Level Input Set-up/Alarm Relay
.