50

v

Level/Start-Stop Set Up Procedure

1. Press [MENU] to enter the { –MENU – } sub-system. Press [UP] or [DOWN] until { –MENU– /

LEVEL SWITCH} screen is displayed.

-MENU-

LEVEL SWITCH

Press [ENTER] to continue to program the Level Switch sub-menu.

2. The level input can be configured as {INACTIVE}, if it will not be used.

LEVEL SWITCH

INACTIVE

Pressing [ENTER] when {LEVEL SWITCH / INACTIVE} is displayed will cause the screen to return
to the { –MENU– / LEVEL SWITCH} screen.

3. Press [UP] to scroll to the next option {LEVEL SWITCH / ACTIVE}.

LEVEL SWITCH

ACTIVE

4. Press [ENTER] when {LEVEL SWITCH / ACTIVE} is displayed and the following screen is

displayed.

LEVEL SWITCH

DRUM LEVEL

Select this option if the level input is to be connected to a drum level switch.

Press [ENTER] to select. Go to step 7.

5. Pressing [UP] when the {LEVEL SWITCH / DRUM LEVEL} screen is displayed will open

the{LEVEL SWITCH / START/STOP} screen.

LEVEL SWITCH

START/STOP

6. Pressing [ENTER] from {LEVEL SWITCH / START/STOP} screen to configure the LEVEL

SWITCH input for use with a remote motor On/Off switch.

7. The Level Switch Configuration screen is displayed:

LEVEL SWITCH

NORMALLY CLOSED

8. Press [ENTER] to configure the switching device as {NORMALLY CLOSED}, or press [UP] and then

press [ENTER] to configure the switching device as {NORMALLY OPEN}.

LEVEL SWITCH

NORMALLY OPEN


When {LEVEL SWITCH / START/STOP} has been selected, you are returned to the {–MENU– /
LEVEL SWITCH} screen. This setting uses the default settings of {MOTOR OFF? / YES} and
{ALARM RELAY? / NO}. These settings cannot be modified.

9. The display prompts for the motor status when the Level Input trips:

LEVEL SWITCH

MOTOR OFF? YES

Press [ENTER] if you want the PULSAR motor to turn off when the Drum Level input is sensed. Go
to step 11.