3 units – Pulsafeeder Pulsar DLC User Manual
Page 73

68
Press [UP] to change the value to {YES}. Press [ENTER] to accept your selection. The following
message is displayed:
PLEASE WAIT
5. The first screen displayed during the Re-Set procedure prompts you to turn the motor on.
TURN MOTOR ON
TESTING ENCODER
6. Press [MOTOR].
You will hear the pump motor spin up, and the DLC will perform an Encoder test (displaying the
following message:)
PLEASE WAIT
TESTING ENCODER
When the Encoder test is complete, (usually takes about 2 or 3 seconds) the DLC performs a Zero
Calibration (displaying the following message:)
PLEASE WAIT
CALIBRATING ZERO
When the Zero Calibration is complete, you are returned to the {–MENU– / FACTORY DEFAULTS}
screen.
Press [MENU] and the next screen displayed is:
MOTOR STOPPED
Re-establish any Menu and Calibration settings that are non-standard at this time..
7.3
Units
By pressing [UNITS] with the motor on, the display will scroll through the CMH, GPH, LPH, CCH,
CMM, GPM, LPM, CCM, % flow, % stroke length or % motor speed. The DLC will automatically
convert the motor and stroke settings based on the calibrated flow, to the above referenced units.
If the {MENU / NUMBER FORMAT} was setup to show only one specific calibrated unit of flow, then
you will have only that unit displayed alternately with the % flow display.
The accuracy of the flow rate display is dependent on the pump flow calibration accuracy.