SUPPORTED FUNCTION CODES and SUB-FUNCTION CODES

0x01

READ COIL STATUS (bits)

SUPPORTED

0x02

READ INPUT STATUS (bits).

SUPPORTED

0x03

READ HOLDING REGISTERS (16-bit integers)

SUPPORTED

0x04

READ INPUT REGISTERS (16-bit integers)

SUPPORTED

0x05

FORCE SINGLE COIL (bits)

NOT supported

0x06

PRESET SINGLE HOLDING REGISTER (16-bit integer)

SUPPORTED

0x07

READ EXCEPTION STATUS (8-bits only)

NOT supported

0x08

DIAGNOSTIC FUNCTIONS

PARTIALLY supported

0x0000

RETURN QUERY DATA (ECHO)

SUPPORTED

0x0001

RESTART COMMUNICATIONS PORT

SUPPORTED

0x0002

RETURN DIAGNOSTIC REGISTER

NOT supported

0x0003

CHANGE ASCII INPUT DELIMITER

SUPPORTED

0x0004

SET LISTEN ONLY MODE

SUPPORTED

0x0005 - 0x0009 reserved

NOT supported

0x000A

CLEAR CTRS AND DIAGNOSTIC REGISTER

NOT supported

0x000B

RETURN BUS MESSAGE COUNT

NOT supported

0x000C

RETURN BUS COMM. ERROR COUNT

NOT supported

0x000D

RETURN BUS EXCEPTION ERROR COUNT

NOT supported

0x000E

RETURN SLAVE MESSAGE COUNT

NOT supported

0x000F

RETURN SLAVE NO RESPONSE COUNT

NOT supported

0x0010

RETURN SLAVE NAK COUNT

NOT supported

0x0011

RETURN SLAVE BUSY COUNT

NOT supported

0x0012

RETURN BUS CHAR. OVERRUN COUNT

NOT supported

0x0013

RETURN OVERRUN ERROR COUNT

NOT supported

0x0014

CLEAR OVERRUN COUNTER AND FLAG

NOT supported

0x0015

GET/CLEAR MODBUS® PLUS STATISTICS

NOT supported

0x0016 - 0xFFFF reserved

NOT supported

0x09

PROGRAM MODICON 484 CONTROLLER

NOT supported

0x0A

POLL MODICON 484 CONTROLLER

NOT supported

0x0B

FETCH COMMUNICATIONS EVENT COUNTER

NOT supported

0x0C

FETCH COMMUNICATIONS EVENT LOG

NOT supported

0x0D

PROGRAM CONTROLLER

NOT supported

0x0E

POLL CONTROLLER

NOT supported

0x0F

FORCE MULTIPLE COILS.

NOT supported

0x10

PRESET MULTIPLE HOLDING REGISTERS

SUPPORTED

0x11

REPORT SLAVE ID

SUPPORTED

------- Return message contains: --------------------------------------------

0x22 =

Byte Count (length of data field to follow) (34 decimal)

0x99 =

Slave ID

0x## =

Run Status (of the pump motor)

0x00=off, 0xFF=on

16 characters from prom_ver[] string like: " 1.24 "

16 characters from Serial Number string entered at Factory Setup

Example: "B156045-D10 "

0x12

PROGRAM 884/M84

NOT supported

0x13

RESET COMMUNICATIONS LINK

NOT supported

0x14

READ GENERAL REFERENCE

NOT supported

0x15

WRITE GENERAL REFERENCE

NOT supported

0x16

MASK WRITE 4X REGISTERS.

NOT supported

0x17

READ/WRITE 4X REGISTERS.

NOT supported

0x18

READ FIFO QUEUE

NOT supported

0x19 to 0x7F are UNUSED

NOT ASSIGNED

Exception:

0x6F is used ONLY for the DLC to DLC MODBUS
Mode.