7.2.1 Alarm, and Error messages

When an error occurs, the DLC flashes Alarm and Error messages alternately with the standard display.
If the error is catastrophic (e.g.; Tachometer Failure), the catastrophic error message will remain
displayed until the problem is repaired.

The following table gives an example of these messages and when you can expect them to be
displayed.

Message

Displayed When:

ANALOG SIG FAIL

The Analog signal has fallen below its calibrated range or has
fallen rapidly (indicating an open circuit).

LEAK DETECTION

The PULSAlarm leak detection diaphragm has failed.*

LEVEL SWITCH

The Drum Level switch has been activated.*

POWER FAILURE

The input power to the DLC was interrupted while the pump
motor was running.*

OVER TEMPERATURE

The internal temperature of the DLC has exceeded its
operating limit.*

ALARM RELAY

If configured, this message is displayed when the alarm relay
activates.

*DUTY CYCLE*

When displayed, indicates that the stroke adjustment motor
has run continuously for more than 20 minutes and is now in
a cool down phase.

MOTOR THERMOSTAT

The temperature of the DLC Pump Motor has reached its
operating limit.*

REMOTE ON/OFF

If configured, displays when the remote On/Off switch is in
the Off position.

TERMINATED / PRESS ANY
KEY

The Manual Control Knob moved during calibration.

POSITION ERROR

Motion has not been detected when expected for a fairly long
period of time.

MODBUS SIG FAIL

The digital command was not received within the timeout
limit.

OVER VOLTAGE

The incoming power exceeds the specified range.

UNDER VOLTAGE

The incoming power is below the specified range.

* Refer to the Diagnostics Section (next section) for information on each of these messages.