Pulsafeeder Pulsar DLC User Manual
Page 58

53
v
Digital Output Set Up Procedure
1. Press [MENU] once and then press [UP] or [DOWN] until the display reads {–MENU– / DIGITAL
OUTPUT}.
–MENU–
DIGITAL OUTPUT
2. Press [DOWN]. The {DIGITAL OUTPUT / RUN/STOP STATUS} screen is displayed.
DIGITAL OUTPUT
RUN/STOP STATUS
To use the DIGITAL OUTPUT function as a remote On/Off indication, press [ENTER].
3. Press [ENTER] to continue to program the Digital Output sub-menu. The {DIGITAL OUTPUT /
PUMP STROKE} screen is displayed.
DIGITAL OUTPUT
PUMP STROKE
To use the DIGITAL OUTPUT to indicate pump strokes, press [ENTER]. Go to step 6.
4. Press [DOWN]. The {DIGITAL OUTPUT / MODE INDICATION} screen is displayed.
DIGITAL OUTPUT
MODE INDICATION
To use the DIGITAL OUTPUT function as a Mode Indicator press [ENTER]. The following screens
are displayed:
MODE INDICATION
MANUAL MODE
Press
[UP]
MODE INDICATION
ANALOG MODE
Press
[UP]
MODE INDICATION
MODBUS MODE
Press [UP] or [DOWN] to scroll through the screens shown above. Press [ENTER] to select the
desired option
5. The {DIGITAL OUTPUT / NORMALLY OPEN} screen is displayed.
In this mode, the output is open (non-conducting) when the motor is off or the Mode is wrong
DIGITAL OUTPUT
NORMALLY OPEN
The output is closed (conducting) when the motor is on or the Mode is correct.
Configure the output as {NORMALLY OPEN} by pressing [ENTER]. Go to step 7.
6. Press [UP] to open the {DIGITAL OUTPUT / NORMALLY CLOSED} screen.
In this mode, the output is open (non-conducting) when the motor is on or the Mode is correct.
DIGITAL OUTPUT
NORMALLY CLOSED
The output is closed (conducting) when the motor is off or the Mode is wrong.
Press [ENTER] to configure the output as {NORMALLY CLOSED}.
7. The {–MENU– / DIGITAL OUTPUT} screen is displayed.