beautypg.com

2 pulsar motor – Pulsafeeder Pulsar DLC User Manual

Page 16

background image

11

5.4.2 PULSAR Motor

Connect the pump motor to the J3 terminal block labeled 'PUMP MOTOR OUT AC/DC.' (Use 14
AWG (2.1mm

2

), 105

ø

C insulation wire size or larger.) The pump motor must be wired to operate at

the DLC supply voltage (i.e., if the power supplied to J1 is 115VAC 60Hz, then the motor must operate
on 115VAC at 60Hz).

T

HE

DLC

USES SOLID

-

STATE RELAYS FOR IT

'

S HIGH VOLTAGE OUTPUTS

(

I

.

E

.,

MOTOR AND

ALARM

). I

N THE

'OFF'

STATE

,

THESE DEVICES TYPICALLY LEAK

20-30

M

A

OF CURRENT AT THE

SUPPLY VOLTAGE TO THE ATTACHED DEVICE

(

OR TERMINAL BLOCK

)! T

HE SUPPLY POWER

MUST BE DISCONNECTED AT THE MAIN BEFORE WORKING ON ELECTRICAL CONNECTIONS OR

ANY MOVING PUMP COMPONENTS

(

E

.

G

.,

MOTOR

,

GEAR TRAIN

,

ETC

.).


D

OUBLE CHECK ALL CONNECTIONS TO CONFIRM GOOD ELECTRICAL CONTACT BETWEEN THE

TERMINAL BLOCK CLAMP AND BARE WIRE

. M

AKE SURE THE CLAMP IS ON THE WIRE

,

NOT THE

INSULATION

. I

NSURE THAT BARE WIRE IS NOT FRAYED AND DOES NOT RISE ABOVE DIVIDERS

.

If the PULSAR pump motor is controlled by a Variable Speed Drive (e.g., DC Drive), the Variable
Speed Drive must be powered by the DLC. Wire the Variable Speed Drive to J3. Wire the PULSAR
motor to the Variable Speed Drive in accordance with the Variable Speed Drive manufacturer's
instructions. Refer to Section 8 – Diagrams: Diagram 2 for recommended wiring.

If the PULSAR pump motor or Variable Speed Drive operates at a voltage different than that supplied
to the DLC or is a three-phase motor, then a motor starter must be used. Wire the motor starter relay to
J3. Wire the PULSAR motor or Variable Speed Drive to the motor starter in accordance with the
starter manufacturer's instructions. Refer to Section 8 – Diagrams: Diagram 2 for recommended
wiring.

D

AMAGE MAY OCCUR TO THE

DLC

IF THE

PULSAR

PUMP MOTOR IS NOT WIRED AND

COMMUNICATING WITH THE

DLC.