Pulsafeeder Pulsar DLC User Manual
Page 76
71
v
Batching system Set Up procedure:
1. Press [BATCH], to enter the batch set-up menu.
2. The display will come up as {BATCHES / ACTIVE} or {BATCHES / INACTIVE}. Press [UP] to
change the batch system to {ACTIVE}.
Setting the batch system to ACTIVE will cause any pre-configured batches that are scheduled to start
at this time, to start immediately, so you might want to do this last.
BATCHES
ACTIVE
Press
[UP]
BATCHES
INACTIVE
Press [ENTER] to continue on to the batch sub-menu.
3. The display shows {EDIT / BATCH #1}. Press [UP] to {EDIT / BATCH #2} and [UP] again to
{EDIT / BATCH #3}.
EDIT
BATCH #1
Press
[UP]
EDIT
BATCH #2
Press
[UP]
EDIT
BATCH #3
The DLC is supplied with three user programmable batches. Press [ENTER] to select the desired batch
to edit.
4. The display shows {BATCH #1 RATE / 92.5%} (the value and unit of flow will depend on previous
programming). The {RATE} text will be flashing. You can press [UP] or [DOWN] to view/change
the other menu items related to this batch (e.g., RATE / DURATION / TYPE / START, etc.). Pressing
[ENTER] causes the {RATE} value to stop flashing and allows you to program the batch flow rate.
Press [UP] or [DOWN] to set the value.
If a value has been set previously it will be used as a starting point for the new setting.
You can change the display units at any time by pressing [UNITS].
BATCH #1 RATE
92.5%
Press [ENTER] to accept your setting.
5. The display shows {BATCH #1 DURATION / XX HRS, XX MIN} with the word DURATION
flashing. Press [ENTER] to set the duration (i.e., pump on time) of the batch.
BATCH #1 DURATION
12 HRS 30 MIN
6. The hours value should now be flashing on the display. A line (cursor) under the second digit indicates
the field to be changed. Press [UP] or [DOWN] to scroll through the numbers 0-99. Press [ENTER] to
accept the desired hour setting.
BATCH #1 DURATION
12 HRS 30 MIN