beautypg.com

5 coils, 6 input bits (1x references) – Pulsafeeder Pulsar DLC User Manual

Page 109

background image

104

14.5 Coils

Coils are discrete, single bit outputs like the ALARM OUTPUT and DIGITAL OUTPUT.

Notes:

Read only.

The coil information is packed as 8 coils per byte.

Coils are accessible through Function Code 0x01.

The requested value is returned in the least most significant bit.

Function

Address

DDE Ref.

Purpose

Data Format

Read (0x01)

0x0000

000001

Alarm Output

Bit(0x01 = On)

Read (0x01)

0x0001

000002

Digital Output

Bit(0x01 = On)

14.6 Input Bits (1x references)

Input Bits are discrete, single bit inputs such as the keyboard KEYS, LEAK DETECTION, LEVEL
INPUT and THERMOSTAT inputs.

Notes:

Read only.

The input information is packed as 8 input bits per message byte.

Input Bits are accessible through Function Code 0x02.

The requested value is returned in the least significant bit.

Function

Address DDE Ref.

Purpose

Data Format

READ (0x02)

0x0000

100001

Key Pad Input: START/STOP

Bit(0x01=On)

READ (0x02)

0x0001

100002

Key Pad Input: BATCH

Bit(0x01=On)

READ (0x02)

0x0002

100003

Key Pad Input: UP

Bit(0x01=On)

READ (0x02)

0x0003

100004

Key Pad Input: MENU

Bit(0x01=On)

READ (0x02)

0x0004

100005

Key Pad Input: CALIBRATE

Bit(0x01=On)

READ (0x02)

0x0005

100006

Key Pad Input: DOWN

Bit(0x01=On)

READ (0x02)

0x0006

100007

Key Pad Input: UNITS

Bit(0x01=On)

READ (0x02)

0x0007

100008

Key Pad Input: MODE

Bit(0x01=On)

READ (0x02)

0x0008

100009

Key Pad Input: ENTER

Bit(0x01=On)

READ (0x02)

0x0009

100010

Digital Input: LEAK DETECT
(J4-3, J4-4)

Bit(0x01=On)

READ (0x02)

0x000A

100011

Digital Input: LEVEL INPUT
(J4-5, J4-6)

Bit(0x01=On)

READ (0x02)

0x000B

100012

Digital Input: MOTOR
THERMOSTAT (J10-3, J10-4)

Bit(0x01=On)

READ (0x02)

0x000C

100013

Encoder: Channel B

Bit(0x01=On)

READ (0x02)

0x000D

100014

Encoder: Channel A

Bit(0x01=On)

READ (0x02)

0x000E

100015

Digital Input: Tachometer
(J10-1, J10-2)

Bit(0x01=On)