7.2.9 Motor Thermostat Set Up

This sub-menu allows you to configure the DLC to interact with the pump motor thermostat. The
motor must be equipped with the optional thermostat for this to work.

For equipment safety, the DLC can be programmed to have one of the following responses if the Motor
Thermostat activates:

Shut the motor off, (no alarm) (no restart)

Trigger the alarm relay, (motor stays on)

Shut the motor off and trigger the alarm relay, (no restart)

Shut the motor off, trigger the alarm relay, and then restart the motor when the Motor Thermostat
resets,

Shut the motor off and then restart the motor when the Motor Thermostat resets (No alarm),

Ignore the thermostat input.

v

Motor Thermostat Set Up Procedure

1. Press [MENU] once and then press [UP] or [DOWN] until the display reads {–MENU– / MOTOR

THERMOSTAT}.

–MENU–

MOTOR THERMOSTAT

2. Press [ENTER] and the {MOTOR THERMOSTAT / NORMALLY CLOSED} screen is displayed.

MOTOR THERMOSTAT

NORMALLY CLOSED

Press [ENTER] to accept the {NORMALLY CLOSED} configuration. Go to step 4.

or

Press [UP] and the {MOTOR THERMOSTAT / INACTIVE} screen is displayed.

MOTOR THERMOSTAT

INACTIVE

If the {MOTOR THERMOSTAT} is to be configured as {INACTIVE}, (this is the factory default
setting) press [ENTER] and you are returned to the {–MENU– / MOTOR THERMOSTAT} screen.

I

F YOU SET

{MOTOR THERMOSTAT}

TO

{INACTIVE}

OR SET

{MOTOR OFF?}

TO

{NO},

IT IS POSSIBLE FOR THE MOTOR WINDINGS TO OVERHEAT LEADING TO PREMATURE MOTOR

FAILURE AND POSSIBLE HAZARDOUS CONDITIONS

(

E

.

G

.,

FIRE

).

3. Pressing [UP] from the {MOTOR THERMOSTAT / INACTIVE} screen will display the {MOTOR

THERMOSTAT / NORMALLY OPEN} screen.

MOTOR THERMOSTAT

NORMALLY OPEN

Press [ENTER] to accept the {NORMALLY OPEN} configuration.

4. The {MOTOR THERMOSTAT / MOTOR OFF? YES} screen is displayed.

MOTOR THERMOSTAT

MOTOR OFF? YES

Press [UP] to select between {YES} or {NO}.

If you want the motor to turn off when the thermostat activates, (recommended), set {MOTOR OFF?}
to {YES}.

Press [ENTER] to accept the desired configuration.

5. The {MOTOR THERMOSTAT / ALARM RELAY? YES} screen is displayed.

MOTOR THERMOSTAT

ALARM RELAY? YES

Press [UP] to select between {YES} and {NO}.