beautypg.com

7 level / remote / start – stop set up – Pulsafeeder Pulsar DLC User Manual

Page 54

background image

49

v

Leak Detection Failure Set Up Procedure

1. Press [MENU] to enter the { –MENU– } sub-system. Press [UP] or [DOWN] until {–MENU– / LEAK

DETECTION} is displayed.

-MENU-

LEAK DETECTION

Press [ENTER] to continue to program the Leak Detection options.

2. The Leak Detection Input can be configured as {INACTIVE}. If the pump is not supplied with a

PULSAlarm Leak Detection Diaphragm, it should be set as {INACTIVE}.

LEAK DET INPUT

INACTIVE

Press [ENTER] to accept your selection. The {–MENU– / LEAK DETECTION} screen is displayed.

3. If your pump is supplied with a PULSAlarm Leak Detection Diaphragm, press [UP] to select the type

of switch. The Leak Detection Input switch can be configured as {NORMALLY OPEN},

LEAK DET INPUT

NORMALLY OPEN

or press [UP] to configure the switch as {NORMALLY CLOSED}.

LEAK DET INPUT

NORMALLY CLOSED

Press [ENTER] to accept the desired configuration.

4. The display prompts you to configure the motor state (ON/OFF) should a diaphragm rupture occur (i.e.,

a leak is detected).

LEAK DETECTION

MOTOR OFF? NO

If you do not want the pump's motor to turn off when a leak is detected, press [ENTER] to accept the
default value. If you want the motor to shut off if a leak is detected, press [UP] to scroll to {YES} and
press [ENTER].

5. The display prompts you to configure the alarm relay status (triggered or not triggered).

LEAK DETECTION

ALARM RELAY? NO

If you do not want the Alarm Relay activated when a leak is detected, press [ENTER] to accept the
default of {NO}. If you want the alarm relay to be active if a leak is detected, press [UP] to scroll to
{YES} and press [ENTER]. The display returns to the { –MENU– / LEAK DETECTION} screen.

7.2.7 Level / Remote / Start – Stop Set Up

This sub-menu allows you to configure the DLC to interact with a level input. You can program the
DLC to have one of the following responses:

Shut the motor off,

Trigger the alarm relay,

Shut the motor off and trigger the alarm relay,

Shut the motor OFF when the level input is in one state (e.g. CLOSED) and turn the motor ON
when the level input is in the other state (e.g. OPEN).


The level sensor or Start/Stop switch must be a dry contacting type. Refer to Section 5-Installation:
Low Voltage Input Connections
.


If you select the 'motor off' option, the motor will have to be manually re-started when a Level
Failure is detected (i.e., press [MOTOR] to start the pump motor).