Low Voltage Outputs

Outputs

Field Wiring

Location

Specification / Description

Analog Output Channel

J5 Pin 1 is +
J5 Pin 2 is –

Any signal within the range of 0 – 20mA (e.g.: 4-20).
Minimum span of 2mA.
Maximum load: 700 ohms.

Reverse Acting standard on all units, which is accessible via calibration.
Fused at 50mA protected against mis-wiring.
Surge Protection: 7.4 Joules
Isolation: 500 volts from all inputs and outputs.

Alarm Status

J5 Pin 3 is +
J5 Pin 4 is –

Dry Contact (Transistor Type)
VCE (SAT): 0.3 volts
Max forward current: 50mA
Maximum 32VDC
On-state resistance: 100 ohms
Isolation: 5000 volts from all inputs, outputs and ground.

Follows the state of High Voltage Alarm Output, which may be software
configured as Normally Open or Normally Closed.

Digital Output

Programmable as

Remote Run Status

Or

Stroke Counter

Or

Mode Indication

J5 Pin 5 is +
J5 Pin 6 is –

Dry Contact (Transistor Type)
VCE (SAT): 0.3 volts
Max forward current: 50mA
Maximum 32VDC
On-state resistance: 100 ohms
Isolation: 5000 volts from all inputs, outputs and ground.
May be software configured as Normally Open or Normally Closed.
(Remote Run Status and Mode Indication only).