21

5.10 Fuse Replacement

Although Fuse replacement is not a part of normal installation, it is possible that fuse failure will result
from improper wiring. The DLC uses a total of 7 user replaceable fuses: 1 for the alarm relay output, 2
for each of the Current Input and Output Channels. The table below details fuse replacement information:

Designator

Function

Rating

Wickman P/N

Pulsafeeder P/N

F1

Alarm Relay

1A @ 250VAC

WK4048-ND

NP5300026-000

F2-7

Current I/O

50mA @ 250VAC

WK3022-ND

NP5300027-000

Replacement Fuse Information

Figure 11 details the location of these fuses on the Field Wiring Board.

Figure 11. – Fuse Location.

The Internal DLC power supply is fused at 2 Amps. This fuse is not user serviceable. The DLC Stroke
Length Adjustment Synchronous Motor is inherently protected. It can operate continuously in a locked
rotor state. The DLC also monitors this motor's duty cycle to maintain a 50% balance between ON and
OFF times. The serial ports and the Remote Run Status Output are protected by self-resetting current
limit devices. These components are not user serviceable.