Specifications – Pulsafeeder Pulsar DLC User Manual

Page 82

background image

77

9. Specifications

S

TROKE

L

ENGTH

C

ONTROL

:

0-100% control range
0.1% resolution
10:1 turndown for accuracy specification.

Combined Calibrated Flow:

6 significant digits for displayed units of flow.

Pump Accuracy:

Turndown Range

Accuracy

Standard

Diaphragm

Diaphragm

With Leak

Detection

Single Solid

Teflon

Diaphragm

Capacity

Reference

Stroke

Length

Motor

Speed

Combined

Turndown

Steady State

±

0.5%

±

0.5%

±

0.5%

Set Point

10:1

20:1

50:1

Repeatability

±

0.5%

±

1.0%

±

1.0%

Full Rating

10:1

20:1

50:1

Linearity

±

1.0%

±

3.0%

±

3.0%

Full Rating

10:1

20:1

50:1

Adjustment Response:

1% per second on stroke length.

1% per second on steady state speed.

Temperature:

–18

°

C to 40

°

C (0

°

F to 104

°

F) Operation.

–18

°

C to 60

°

C (0

°

F to 140

°

F) Storage.

Low Voltage Inputs

Inputs

Field Wiring

Location

Specification / Description

Analog Input

J4 Pin 1 is +
J4 Pin 2 is –

Any signal within the range of 0 to 25mA (e.g.: 4-20)
or 0 to 5 volts (e.g.: 1-5)
Minimum span of 2mA or 0.4 volts.
Note: No jumpers used. Displayed in mA.

Split Ranging, Reverse Acting and Ratio Control standard on all
units; accessible via calibration.

Fused at 50mA. Protected against mis-wiring.
Surge Protection: 7.4 Joules
Isolation: 500 volts from all other inputs, outputs, and ground.

PULSAlarm
(Leak Detection)

J4 Pin 3 is +
J4 Pin 4 is –

Dry Contact. (Optically Isolated) – Do not apply powered signal.
Isolation: Not isolated from Digital Input or Motor Thermostat, 500

volts from all other inputs, outputs and ground.

May be software configured as Normally Open or Normally Closed.
May be software configured to operate the Alarm Relay.
May be configured to turn the Pump Motor off.

Digital Input

Programmable as

Level Input

Or

Remote Run / Stop

J4 Pin 5 is +
J4 Pin 6 is –

Dry Contact. (Optically Isolated) – Do not apply powered signal.
Isolation: Not isolated from PULSAlarm or Motor Thermostat, 500 volts

from all other inputs, outputs and ground.

May be software configured as Normally Open or Normally Closed.
May be software configured to operate the Alarm Relay (Level Input
Only).
May be configured to turn the Pump Motor off. (Level Input Only)