7.2.11 Power Failure Set Up

This sub-menu allows you to configure the way the DLC reacts when power is restored after a power
outage. Additionally this sub-menu allows setting the action to take if improper voltage is applied.
During the power up stage, the DLC can either:

Return to settings that were active when the pump lost power.

Shut the motor off.


A power outage is defined as the loss of power whenever the DLC is not in the {MOTOR OFF} state.

v

Power Failure Set Up Procedure

1. Press [MENU] once and then [UP] or [DOWN] until the display reads {–MENU– / POWER

FAILURE}.

-MENU-

POWER FAILURE

Press [ENTER] to go the power failure response sub-menu.

2. The display prompts you for the Power-up status. To shut the motor off when the power is returned to

the unit (after a power failure), select the {MOTOR OFF} option (factory default).

DURING POWER UP

MOTOR OFF

Press [ENTER] to accept. Go to step 4.

3. If you want to return to the prior settings, press [UP] and scroll to {DURING POWER UP / PRIOR

SETTINGS}.

DURING POWER UP

PRIOR SETTINGS

Press [ENTER] to accept.

4. The display prompts you for an action to take when the wrong voltage is detected.

WRONG VOLTAGE

HARD SHUT DOWN

The following options are available:

Selection

Action

Display under/over voltage message.
Turn motor off.
Inhibit motor operation. (Motor Key Disabled)

Hard Shutdown

Voltage correction and power cycle required to reset alarm.
Display under/over voltage message.

Motor Off

Turn motor off.

Message Only

Display under/over voltage message.

Ignore Error

None

Press [UP] or [DOWN] to make your selection. Press [ENTER] to accept your selection.

5. The display will return to the {–MENU– / POWER FAILURE} screen.