11 power failure set up, Selection action – Pulsafeeder Pulsar DLC User Manual
Page 61

56
7.2.11 Power Failure Set Up
This sub-menu allows you to configure the way the DLC reacts when power is restored after a power
outage. Additionally this sub-menu allows setting the action to take if improper voltage is applied.
During the power up stage, the DLC can either:
−
Return to settings that were active when the pump lost power.
−
Shut the motor off.
A power outage is defined as the loss of power whenever the DLC is not in the {MOTOR OFF} state.
v
Power Failure Set Up Procedure
1. Press [MENU] once and then [UP] or [DOWN] until the display reads {–MENU– / POWER
FAILURE}.
-MENU-
POWER FAILURE
Press [ENTER] to go the power failure response sub-menu.
2. The display prompts you for the Power-up status. To shut the motor off when the power is returned to
the unit (after a power failure), select the {MOTOR OFF} option (factory default).
DURING POWER UP
MOTOR OFF
Press [ENTER] to accept. Go to step 4.
3. If you want to return to the prior settings, press [UP] and scroll to {DURING POWER UP / PRIOR
SETTINGS}.
DURING POWER UP
PRIOR SETTINGS
Press [ENTER] to accept.
4. The display prompts you for an action to take when the wrong voltage is detected.
WRONG VOLTAGE
HARD SHUT DOWN
The following options are available:
Selection
Action
Display under/over voltage message.
Turn motor off.
Inhibit motor operation. (Motor Key Disabled)
Hard Shutdown
Voltage correction and power cycle required to reset alarm.
Display under/over voltage message.
Motor Off
Turn motor off.
Message Only
Display under/over voltage message.
Ignore Error
None
Press [UP] or [DOWN] to make your selection. Press [ENTER] to accept your selection.
5. The display will return to the {–MENU– / POWER FAILURE} screen.