Warning, Pwr b, Chapter 2: installation 66 – Allied Telesis AT-CV5000 User Manual
Page 66: 60vdc warning

Chapter 2: Installation
66
Figure 43. Inserting Wires into a DC Terminal Block
6. Connect the +48 VDC (RTN) feed wire to the terminal block marked
+ (plus).
7. Connect the -48 VDC feed wire to the terminal block marked - (minus).
8. Secure the tray cable near the rack framework using multiple cable
ties to minimize the chance of the connections being disturbed by
casual contact with the wiring. Use at least four cable ties, separated
four inches apart. Locate the first one within six inches of the terminal
block.
9. Ensure that the circuit breaker is in the OFF position.
10. Connect the supply-cable wires to the circuit breaker.
11. Energize the circuit breaker.
12. Turn the power switch to the ON position.
If you installed an optional redundant power supply, repeat this procedure
to attach DC wires to the second terminal block.
B
WR15
e pow
er in
put. To
isconn
ect all p
ower
FOR C
ENTR
ALIZ
ED D
C PO
WER
CONN
ECTIO
N, INS
TALL
ONLY
IN
A RE
STRIC
TED A
REA.
POWER
FAULT
AT-PWR15
A
B
AT-CVFAN
A
AT-CVFAN
B
AT-PWR15
POWER
FAULT
40-60VDC
WARNING
This unit might have more than one power input. To
reduce the risk of electric shock, disconnect all power
inputs before servicing unit.
FOR CENTRALIZED DC POWER
CONNECTION, INSTALL ONLY IN
A RESTRICTED AREA.
40-60VDC
WARNING
This unit might have more than one power input. To
reduce the risk of electric shock, disconnect all power
inputs before servicing unit.
FOR CENTRALIZED DC POWER
CONNECTION, INSTALL ONLY IN
A RESTRICTED AREA.
256
PWR B
Warning:
Check to see if there are any exposed copper strands
coming from the installed wires. When this installation is done
correctly there should be no exposed copper wire strands
extending from the terminal block. Any exposed wiring can con-
duct harmful levels of electricity to persons touching the wires.
E12
This system will work with a positive grounded or negative
grounded DC system. E13