Display Messages

C-6

HP StorageWorks Modular Smart Array 500 System User Guide



Table C-1: Display Messages

continued

Message Type

Description Action

44 REDUNDANCY
FAILED MISMATCH
HARDWARE

Error

Both array controllers
must contain the same
hardware for them to
successfully enter
redundant mode. The
current array controllers
do not contain the same
hardware, possibly
because one has an
attached fibre daughter
card and the other does
not.

If the MSA500 system is
currently involved in host
I/O:

1.

Remove the standby

array controller.

2.

Add or replace the fibre

daughter card as
needed.

3.

Wait 10 seconds.

4.

Reinstall the controller,

and be sure that it
seats fully in the
chassis.

If this action does not solve
the problem, wait until
downtime is available and
do the following:

1.

Power down the

MSA500 system.

2.

Remove both array

controllers.

3.

Add or remove fibre

daughter cards as need
on both controllers.

4.

Reinstall both array

controllers, and be sure
that they seat fully in
the chassis.

If this action does not solve
the problem, contact HP
support.

continued