beautypg.com

7 changing the default power up settings, Changing the default power up settings -20, R. 3.3.7). t – KEPCO BOP 1KW-MG Operator Manual, Firmware Ver.2.01 to 2.37 User Manual

Page 80: R. 3.3.7, Ar. 3.3.7), E 3-6 fo

background image

3-20

BOP HIPWR 022108

BATTERY

. This mode is necessary for the power supply to function properly and safely with

either battery or constant-voltage-type active electronic loads. This mode prevents the battery
from discharging during the OFF state. When the output is disabled (set to OFF), the BOP will
go to current mode, current will be set to zero, with voltage protect and current limit set to maxi-
mum. In this way the battery will not be discharged while the output is OFF. For constant-volt-
age-type active electronic loads this mode stops energy flow during the OFF state. Table 3-6
indicates how the power supply responds to a command to go from Output ON to OFF.

To configure, press

%

from the power-up screen, then highlight Load Type and press

!

to

modify. (If a Password is required, see PAR. 3.2.4.4 for instructions.) Highlight Active, Resistive
or Battery (see explanations and associated WARNINGS above) and press

$

to save. Then

press

$

to save for power-up,

#

to abort, or

%

to apply the changes (without saving for

power-up) and exit. After configuring, the new setting will be effective when the power supply
goes from output on to output off.

To restore factory default (Active), press

%

from the power-up screen, highlight Load Type,

press

!

, then press

@

to restore default. Press

$

to save for power-up or

%

to exit

3.3.7

CHANGING THE DEFAULT POWER UP SETTINGS

When the BOP is shipped, the following default settings are programmed to be in effect each
time the unit is turned on, however these defaults may be changed as indicated below;

• Mode: Voltage (may be voltage or current, see PARs. 3.3.2 and 3.4.2. Table 3-7 illus-

trates the relationship between Mode, Main Channel, Protection Type and Levels set-
tings.

• Main Channel: Internal (may be Internal, External, or External Reference Level, PARs.

3.3.3 and 3.4.3).

• Protection type: Internal (may be Internal, External, Lesser Limit) (see PARs. 3.3.3 and

3.4.4)

• Levels, Voltage and Current: maximum (see PAR. 3.4.4) Represents the power-up val-

ues for protection limit channels (bipolar limits), voltage for current mode and current for
voltage mode. Table 3-7 illustrates the relationship between Mode, Main Channel, Pro-
tection Type and Levels settings.

• Output: on (may be on or off) (see PAR. 3.3.5)

To change the default settings refer to the applicable paragraph(s) specified above as needed,
then from the power-up screen press

%

. Highlight Power-up Settings and press

!

. (If a Pass-

TABLE 3-6. POWER SUPPLY BEHAVIOR WHEN OUTPUT IS SET TO OFF

LOAD TYPE

SETTING

If unit was in Voltage Mode when output OFF

command issued.

If unit was in Current Mode when output OFF

command issued.

ACTIVE

• Unit remains in voltage mode.
• Voltage set to zero.
• Both ± Current Protect set to maximum.
• Both ± Voltage Limit. remain at maximum.

• Unit set to voltage mode.
• Voltage set to zero.
• Both ± Current Protect. remain at maximum.
• Both ± Voltage Limit set to maximum.

RESISTIVE

• Unit remains in voltage mode.
• Voltage set to zero.
• Both ± Current Protect set to minimum box values.
• Both ± Voltage Limit. remain at maximum.

• Unit set to voltage mode.
• Voltage set to zero.
• Both ± Current Protect set to minimum box values.
• Both ± Voltage Limit set to maximum,

BATTERY

• Unit set to current mode.
• Current set to zero.
• Both ± Voltage Protect. remain at maximum.
• Both ± Current Limit set to maximum.

• Unit remains in current mode,
• Current set to zero.
• Both ± Voltage Protect set to maximum.
• Both ± Current Limit remain at maximum.