7. Connect a 0V ±0.1mV d-c reference to pin 11 (EXT_REF) referenced to pin 4 (SGND) of the

Analog I/O Port connector (A2A5J6). Set the BOP to zero volts output by sending

CAL:VEXT

ZERO

. Connect the DVM to the BOP output and send

CAL:DATA

commands as needed (see

PAR. 4.3c) to adjust the BOP output until the DVM reads as close to zero as possible within
tolerance specified in Table 4-3 for VOLTAGE ZERO.

NOTE: Accuracy of the 10V d-c reference must be ±0.1mV in order for the calibrated unit to
meet published specifications.

8. Replace 0V reference at pin 11 (EXT_REF) of the Analog I/O Port connector (A2A5J6) with

a +10V d-c reference. Set the BOP to maximum positive output voltage by sending

CAL:VEXT MAX

. Measure the voltage output using the DVM. To adjust, send

CAL:DATA

commands as needed (see PAR. 4.3b) until the DVM reading is as close as possible above
the nominal full scale value within the tolerance specified in Table 4-3 for +FULL SCALE
VOLTAGE.

9. Replace +10V reference at pin 11 (EXT_REF) of the Analog I/O Port connector (A2A5J6)

with a 0V ±0.1mV d-c reference. Set the BOP to zero volts output by sending

CAL:VGA

ZERO

. Connect DVM to the BOP OUT S and OUT COM terminals to measure the output volt-

age. Send

CAL:DATA

commands as needed (see PAR. 4.3c) to adjust the BOP output until

the DVM reads as close to zero as possible within tolerance specified in Table 4-3 for VOLT-
AGE ZERO.

10.Replace 0V reference at pin 11 (EXT_REF) of the Analog I/O Port connector (A2A5J6) with

a +10V d-c reference. Set the BOP to maximum positive output voltage by sending

CAL:VGA

MAX

. Measure the output voltage using the DVM. To adjust, send

CAL:DATA

commands as

needed (see PAR. 4.3b) until the DVM reading is as close to zero as possible within toler-
ance specified in Table 4-3 for VOLTAGE ZERO.

11. Set the BOP to zero volts output by sending

CAL:VLIM ZERO

. Disconnect the +10V d-c ref-

erence voltage from the analog I/O port external reference pin (A2A5J6 pin 11) of the BOP,
then connect 0V ±0.1mV d-c reference voltage from the external voltage source to
VLIM+_EXTERNAL and VLIM–_EXTERNAL (pins 14 and 6) referenced to pin 12 (GND1) of
the BOP analog I/O connector (A2A5J6), then send the

CAL:ZERO

command. This

enables

the BOP to recognize that the voltage at the VLIM_EXTERNAL pins is 0V.

12.Connect +10.0V ±0.1mV d-c reference voltage from the external voltage source to

VLIM+_EXTERNAL and VLIM-_EXTERNAL (pins 14 and 6) referenced to pin 12 (GND1) of
the BOP analog I/O connector (A2A5J6), then send

CAL:VLIM MAX

, then

CAL:ZERO

com-

mands. This enables the BOP to recognize that the voltage at the VLIM+_EXTERNAL pin is
10.0V.

13.Set the BOP to minimum (maximum negative) output by sending

CAL:VLIM MIN

, then send

the

CAL:ZERO

command. This enables the BOP to recognize that the voltage at the VLIM-

_EXTERNAL pin is 10.0V.

14.Connect a 0V ±0.1mV d-c reference to pin 8 (S_IN_SERIAL) of the PAR/SER CONTROL IN

connector (A2A5J3) referenced to COM S terminal at the rear panel (use mating connector
supplied with the unit, P/N 142-0488 to gain access to PAR/SER CONTROL IN connector
pins). Set the BOP to zero volts output by sending

CAL:SER ZERO

. Connect the DVM to the

BOP OUT S and OUT COM terminals and send

CAL:DATA

commands as needed (see

PAR. 4.3b) to adjust the BOP output until the DVM reads as close to zero as possible within
tolerance specified in Table 4-3 for VOLTAGE ZERO.