beautypg.com

Figure 4-1. calibration setup, Calibration setup -6 – KEPCO BOP 1KW-MG Operator Manual, Firmware Ver.2.01 to 2.37 User Manual

Page 130

background image

4-6

BOP-1K 022108

2. For FULL SCALE calibration adjust the output to obtain the closest value above

the nominal full scale value.

3. Set the unit for local sensing with GND Network in (see Figure 4-1) and discon-

nect load from BOP output to prepare the unit for voltage calibration.

FIGURE 4-1. CALIBRATION SETUP

1. Initiate calibration by sending the SCPI command

SYSTem:PASSword:CENable DEFAULT

and then send

CAL:STATe 1

. The password

DEFAULT

has been set at the factory. If the

password has been changed from

DEFAULT

, substitute the correct password for the unit in

the

SYST:PASS:CEN

command. If the password has been lost, consult factory.

2. Set the BOP to zero volts output by sending

CAL:VOLT ZERO

. Connect a Digital Voltmeter

(DVM) to the BOP OUT S and COM S terminals to measure the output voltage. Send

CAL:DATA

commands as needed (see PAR. 4.3c) to adjust the BOP output until the DVM

reads as close to zero as possible within tolerance specified in Table 4-3 for VOLTAGE
ZERO.

3. Set the BOP to maximum positive output voltage by sending

CAL:VOLT MAX

. Measure the

voltage output using the DVM. To adjust, send

CAL:DATA

commands as needed (see PAR.

4.3b) until the DVM reading is as close as possible above the nominal full scale value within
the tolerance specified in Table 4-3 for +FULL SCALE VOLTAGE.

4. Set the BOP to maximum negative output voltage by sending

CAL:VOLT MIN

. To adjust,

send the

CAL:DATA

command as needed (see PAR. 4.3b)

until the reading is as close as

possible above (absolute value) the nominal full scale value within the limits specified in
Table 4-3 for –FULL SCALE VOLTAGE.

5. Send

CAL:VPR MAX

to adjust the maximum positive voltage protection limit of the power

supply. Send the

CAL:DATA

commands as needed (see PAR. 4.3c)

until the reading is as

close as possible above the nominal full scale value within the limits specified in Table 4-3 for
+FULL SCALE VPR LIMIT.

6. Send

CAL:VPR MIN

to adjust the maximum negative protection limit of the power supply.

Send the

CAL:DATA

commands as needed (see PAR. 4.3c)

until the reading is as close as

possible above (absolute value) the nominal full scale value within the limits specified in
Table 4-3 for –FULL SCALE VPR LIMIT.