List of warnings and cautions – KEPCO BOP 1KW-MG Operator Manual, Firmware Ver.2.01 to 2.37 User Manual

Page 8

background image

F

BOP 36-28MG2/21/08

LIST OF

WARNINGS AND CAUTIONS

PAGE

WARNING/CAUTION

2-8

CAUTION:

When working with active loads, the voltage or current of the active load

must not exceed the maximum voltage or current rating of the BOP. Oth-

erwise the overvoltage or overcurrent protection will shut down the pow-

er supply.

2-10

CAUTION:

Never connect the load to the sense terminals. Monitoring instruments

(e.g., DVM, etc.) are the only external equipment that may be safely con-

nected to the sense terminals.

2-10

CAUTION:

The safety features incorporated into the BOP to handle energy from Ac-

tive loads are unable to protect the power supply or the load if input pow-

er to the BOP is lost or if the BOP Malfunctions. It is recommended that

the user monitor “Power OK” flag pins 3 and 4 of the external Protect Port

(see Table 2-4) and implement a fast-acting means of disconnecting ca-

pacitive loads or crowbarring inductive loads to prevent damage to both

the BOP and the load in the event of input power loss.

2-13

CAUTION:

For parallel configurations, Remove links between (COM S) and (COM

OUT) terminals of all slaves to prevent damage to the unit and maintain

system accuracy.

2-13

CAUTION:

Connecting multiple units to different a-c input sources may damage the

BOP power supplies and/or the load.

2-19

CAUTION: The units are now configured as slave(s) to be controlled only by the master.

Do not use the slave keypad, RS 232 port or GPIB port to try to control the

slave(s).

3-3

CAUTION:

Pressing RESET will cause voltage transients to appear at the output

which may damage a connected load.

3-12

CAUTION:

When the ADJUST control is rotated, the active parameter is immediately

effective if the output is enabled (on = STANDBY indicator not lit). The

voltage/current applied to the load changes as the ADJUST control is ro-

tated.

3-18

CAUTION:

When working with active loads, always adjust the BOP protection limits

to be above the maximum values of voltage or current expected from the

load. For example, when the BOP is operating in voltage mode sinking

energy from a constant current type load, set the current protection limits

of the BOP above the maximum current expected from the load.

3-24

CAUTION:

Before Pressing

@

to enter the Saved Waveform Screen from the power-

up screen, perform the following steps to avoid unexpected voltages or

currents from previous settings being briefly applied to the load when the

waveform is first executed.

3-33

CAUTION:

Pressing RESET will cause voltage transients to appear at the output

which may damage a connected load. Switch is recessed to prevent inad-

vertent activation.

3-50

CAUTION:

When the serial port has received an XOFF, the error message -400, QUE

error will be placed in the queue to indicate the loss of transmitted infor-

mation due to a received XOFF character. When XON is received, the unit

will transmit all data in it's buffer followed by the exclamation character

(!). This (!) character is not part of any message from the BOP and indi-

cates the transmission buffer has been cleared and the BOP is idle.

4-12

CAUTION:

If the CALIBRATE ZERO

!

function is available, perform this function

first, as it affects all other output calibrations.