Index – Yokogawa Button Operated DX2000 User Manual
Page 86
3-25
IM 04L41B01-62EN
1
2
3
4
5
Index
Detailed Information for
Attributes of Screens and Components
Attribute
Set value/choice
(Underlined items are initial
set values)
Description, conditions
Alarm level
[1], [2], [3], [4], [All]
The assigned alarm level is set.
All: This becomes ON when an alarm occurs for any one of Alarm
level 1 to 4.
Text indicating the alarm kind is not displayed.
Text showing the alarm kind is not displayed when Channel alarm is
OFF.
Color
[Red], [Orange], [Lime],
[Yellow], [Pink], [Black],
[White]
This is the color for display when no alarm has occurred.
Level 1
[Red], [Orange], [Lime],
[Yellow], [Pink], [Black],
[White], [ALARM]
This is the character color for display at the time of occurrence of a
level 1 alarm.
ALARM: This is the alarm display color set for each alarm level.
The alarm levels are [1] and [All].
Level 2
Same choice as for “level 1”
This is the character color for display at the time of occurrence of a
level 2 alarm.
ALARM: This is the alarm display color set for each alarm level.
The alarm levels are [2] and [All].
Level 3
Same choice as for “level 1”
This is the character color for display at the time of occurrence of a
level 3 alarm.
ALARM: This is the alarm display color set for each alarm level.
The alarm levels are [3] and [All].
Level 4
Same choice as for “level 1”
This is the character color for display at the time of occurrence of a
level 4 alarm.
ALARM: This is the alarm display color set for each alarm level.
The alarm levels are [4] and [All].
Alarm kind display
[Off], [On]
This selects display (On) / no display (Off) of strings that indicate
alarm kind.
Synchronize action
►Section 3.3