23 attributes of modbus in component, 23 attributes of modbus in component -47, Index – Yokogawa Button Operated DX2000 User Manual
Page 108
3-47
IM 04L41B01-62EN
1
2
3
4
5
Index
Detailed Information for
Attributes of Screens and Components
3.23 Attributes of Modbus In Component
(Can only be set with a Version 4.01 screen and a Version 4.11 screen)
The displayed width of the component frame is 1 dot for the DX1000 and 2 dots for the
DX2000.
The following restrictions apply to the attribute settings of Modbus In components.
• [Visible] can only be set when [Depend ID] is set to [None].
• [Maximum] and [Minimum] are not interchangeable.
• If a value smaller than [Minimum] is input for [Maximum], [Minimum] becomes that
value.
• If a value larger than [Maximum] is input for [Minimum], [Maximum] becomes that
value.
List of Settings
Refer to Section 3.3 for attributes without explanations in the list of settings.
Attribute
Set value/choice
(Underlined items are initial
set values)
Description, conditions
X
DX1000: 0 to 318
DX2000: 0 to 638
This is the X-coordinate of the left side of the component.
X = 0 for X < 0
X = (Max.
width
*1
– Width) for (X + Width) > Max. width
*1
Y
DX1000: 24(0) to 238
DX2000: 40(0) to 478
( ) = Status area set to No
display
This is the Y-coordinate of the upper side of the component.
Y = Min. Y
*2
for Y < Min. Y
*2
Y = (Min. Y
*2
+ Max. height
*3
– Height) for (Y + Height) > (Min. Y
*2
+
Max. height
*3
)
*1
DX1000 max. width = 320, DX2000 max. width = 640
*2
DX1000 min. Y = 24(0), DX2000 min. Y = 40(0), ( ) = Status area set to No display
*3