Hazardous area, Safe area rotamass /kf2 – Yokogawa RotaMASS 3-Series User Manual
Page 51

4. INSTAllATION
4-23
IM 01R04B04-00E-E 8th edition March 01, 2011 -00
All Rights Reserved. Copyright © 2003, Rota Yokogawa
pulse output :
The intrinsic safe pulse output is passive and an external power supply with shunt-diode type barrier or
isolation type barrier should be connected.
Maximum voltage : 30 V DC
Maximum current : 100 mA
Example of installation :
Hazardous area
Pout 1 +
Pout 1 -
R barrier
R load
Vin
counter
V out
Ground
Safe area
ROTAMASS
/KF2
F420.EPS
Power supply range
: 10.5 V … 30 V DC
for Not-HART application
Power supply range
: 16.75 V … 30 V DC
for HART application
Load resistance
: 20 … 600 Ω
for Not-HART application
Load resistance
: 230 … 600 Ω
for HART application
Load resistance vs Power supply voltage :
800
700
600
500
400
300
200
100
0
10
12
14
16
18
20
22
24
26
28
30
Load
resistance [ Ω ]
Power supply voltage [V]
HART communication available range
F419.EPS
- EJA120A (79 pages)
- EJA130A (2 pages)
- EJA130A (4 pages)
- EJA120A (31 pages)
- EJA130A (47 pages)
- EJA120A (40 pages)
- EJA438 (5 pages)
- EJA120A (6 pages)
- EJA115 (85 pages)
- EJA120A (47 pages)
- EJA210A (70 pages)
- EJA130A (4 pages)
- EJA430A (78 pages)
- EJA210E (89 pages)
- EJA210E (170 pages)
- EJX120A (4 pages)
- EJA210E (9 pages)
- EJX115A (55 pages)
- EJA210E (41 pages)
- EJA210E (96 pages)
- EJA210E (52 pages)
- EJX910A (9 pages)
- EJX910A (103 pages)
- FlowNavigator Software (163 pages)
- EJX910A (55 pages)
- EJX910A (175 pages)
- EJX910A (83 pages)
- EJA530A (67 pages)
- EJA120A (83 pages)
- EJX530A (52 pages)
- EJA110E (4 pages)
- EJA110E (85 pages)
- EJX120A (85 pages)
- EJA118 (76 pages)
- EJX118A (64 pages)
- EJA438 (72 pages)
- EJA430E (85 pages)
- EJX430A (76 pages)
- EJA430E (7 pages)
- EJX430A (6 pages)
- EJX430A (40 pages)
- EJA430E (96 pages)
- EJA430E (41 pages)
- EJX438A (10 pages)
- ADMAG AXR (194 pages)