beautypg.com

3 iecex, 1 technical data, 3 iecex -19 – Yokogawa RotaMASS 3-Series User Manual

Page 211: 1 technical data -19

background image

9. EXplOSION prOTECTEd TYpE INSTrUMENTS

9-19

All Rights Reserved. Copyright © 2003, Rota Yokogawa

IM 01R04B04-00E-E 8th edition March 01, 2011 -00

remote converter rCCF31 (option /EF2):
- Flame proof with intrinsic safe connection to
detector (ib)
- Additional intrinsic safe outputs.
- II 2G Ex d(e) [ia] [ib] IIC T6
- II 2G Ex d(e) [ia] [ib] IIB T6 with option /HP
Protection [ia] refers to the intrinsic safe outputs.
Protection [ib] refers to the connection
to the detector.
-

II 2D Ex tD [ibD] A21 IP6x T75°C

- Max. surface temperature : 75°C
- Degree of protection : IP67
- Power supply : 90 to 250 V AC, 50/60 Hz

20.5 to 28.8 V DC

- Power consumption : max. 25 VA / 10 W
- Ambient humidity : 0 to 95% RH
- Ambient temperature range : -40°C to +55°C

remote converter rCCr31 (option /ES1:
- Associated apparatus with intrinsic safe

connection to detector (ib)
- II (2)G [Ex ib] IIC
- II (2)G [Ex ib] IIB with option /HP
- II (2)D [Ex ibD]
- Power supply : 90 to 250 V AC, 50/60 Hz

20.5 to 28.8 V DC

- Power consumption : max. 25 VA / 10 W
- Ambient humidity : 0 to 95% RH
- Ambient temperature range : -40°C to +55°C

WARNING


Remote rack mount converter RCCR31 must only
be installed in safe area !

9.3 IECEx

WARNING

Only trained persons use this instrument in
industrial locations.

9.3.1 Technical data

Applicable Standard:
IEC 60079-0: 2004, IEC 60079-1: 2007,
IEC 60079-7: 2006, IEC 60079-11: 2006,
IEC 61241-0: 2004, IEC 61241-1: 2004,
IEC 61241-11: 2005

Certificate: IECEx KEM 06.0031X

remote detector rCCS30 ... 39/Xr (option /ES1):
- Intrinsically safe
- II 2G Ex ib IIB/IIC T1 ... T6
- II 2D Ex ibD 21 IP6x Txxx (xxx = max.

surface temperature see below)
- Max. surface temperature :

Standard

: 150°C

/MT

: 220°C

/HT

: 350°C

- Degree of protection : IP67
- Ambient humidity

: 0 to 95% RH

- Ambient temperature range
Standard and option /MT : -50°C to +80°C
Option /HT (process temperature < 280°C

-50°C to +65°C

Option /HT (process temperature < 350°C

-50°C to +55°C

- Process temperature limits :
Standard

: -50°C to 150°C

Option /MT:

: -50°C to 220°C

Option /HT

: 0°C to 350°C

- Heat carrier fluid temperature limits :
Standard

: -50°C to 150°C

Option /MT:

: -50°C to 220°C

Option /HT

: 0°C to 350°C

remote converter rCCF31 (option /EF1):
- Flame proof with intrinsic safe connection to
detector (ib)
- II 2G Ex d(e) [ib] IIC T6
- II 2G Ex d(e) [ib] IIB T6 with option /HP
-

II 2D Ex tD [ibD] A21 IP6x T75°C

- Max. surface temperature : 75°C
- Degree of protection : IP67
- Power supply : 90 to 250 V AC, 50/60 Hz

20.5 to 28.8 V DC

- Power consumption : max. 25 VA / 10 W
- Ambient humidity : 0 to 95% RH
- Ambient temperature range : -40°C to +55°C