Important – Yokogawa EJX930A User Manual
Page 73
<5. Operational Flowchart>
5-11
IM 01C25R51-01E
Step 3 Download to Device
Perform “Download to Device”. “Device Flow Parameters” will then be downloaded together with
the “Device General Parameters” to the device.
IMPORTANT
For F
OUNDATION
Fieldbus, following block must be checked on the “Download blocks” menu in
the Offline Parameter screen to download “Device Flow Parameters” set by Flow Configuration
Wizard.
EJX910 F
OUNDATION
fieldbus DTM: FTB block
DYF(SoftDL) F
OUNDATION
fieldbus DTM: AR block
“Download blocks” menu
(EJX910 F
OUNDATION
fieldbus DTM)
“Download blocks” menu
(DYF(SoftDL) F
OUNDATION
fieldbus DTM)
F0508E.ai
Figure 5.1 “Download blocks” menu in the Offline Parameter
Offline Parameter
Flow Configuration Wizard
Offline Parameter
Offline
Database
Offline
Database
Offline
Database
Step 1
Step 2
Step 3
Device General Parameters (Default value: , Configured value: )
Device Flow Parameters (Default value: , Configured value: )
*: Confirm the checkbox on the “Download blocks” menu in the Offline Parameter (refer to Figure 5.1)
*
F0509E.ai
Figure 5.2
Procedure to Download the Parameters to the Device