<8. Operation of DYFMVTool>
8-24
IM 01C25R51-01E
Step 5 Confirm input conditions in AR Block
Confirm that the following parameters are the same values input in
“Input.Value”, “Input1.Value” and “Input2.Value”
([Online Parameter] → [Arithmetic] → [Dynamic Variables])
Refer to Table 8.10.
IMPORTANT
Set "Good" status in the following parameters before inputting values:
“Input.Status”, “Input1.Status” and “Input2.Status”
([Online Parameter] → [Arithmetic] → [Configuration] → [Input Parameters])
IMPORTANT
In DYF(SoftDL) F
OUNDATION
fieldbus DTM, "Input.Value", "Input1.Value" and "Input2.Value" are
defined as non-volatile parameters.
In Device DTM, the update time for non-volatile parameters on the Online Parameter screen is
set to 300 seconds as default. Set the value of "Refreshtime for STATICs" to about 30 seconds
because longer time is needed to display parameters in the default configuration.
(Device DTM menu: [Device] → [Additional functions] → [Communication])
Step 6 Confirm output in AR Block
Refer to section 8.3.1