<5. Operational Flowchart>
5-4
IM 01C25R51-01E
(C) Configure with existing Configuration File (XMV file)
Step
FieldMate Menu
EJX910 HART/F
OUNDATION
fieldbus DTM
Layer1
Layer2
Layer3
EJXMVTool
Main Window
Description
"Online Parameter" is opened.
Upload "Device Flow Parameters"
and "Device General Parameters".
Edit "Device General Parameters"
and Apply "Offline Database".
"Import -> Import XMV Menu"
Import "User Flow Parameters"
and "Device Flow Parameters"
from existing file (*.xmv file).
Confirm / Modify compensation
mode.
Confirm / Modify "User Flow
Parameters".
Confirm / Modify "User Flow
Parameters".
Confirm / Modify "User Flow
Parameters".
Confirm / Modify "User Flow
Parameters" and "Device Flow
Parameters".
"Export -> Export XMV Menu"
Export "User Flow Parameters"
and "Device Flow Parameters" to
binary file.
Download
"Device Flow Parameters" and
"Device General Parameters".
Check the flow coefficient.
The value is saved in a log file.:
"FlowCoeffLog"
"Report Menu"
Export "User Flow Parameters" in
CSV file format.
Apply "Device Flow Parameters"
to "Offline Database".
Goes offline.
1
Start DTM and
upload
parameter
from the
device
Import
existing
file and
confirm /
modify flow
configuration
Download
parameter to
the device
Confirm flow
coefficient
2
3
4
Device
Device
Parameter
Offline
Parameter
Flow
Configuration
Wizard
Flow
Configuration
Mode
Primary
Device and
Pipe Setup
Fluid Type
Setup
Fluid
Operating
Range Setup
Fluid Physical
Property
Setup
Apply Flow
Configuration
Assigned DTM
Device
Download to
device 2)
Upload from
device 1)
Additional
Functions
Additional
Functions
Obtain Flow
Coefficient
Disconnect
Device
F0503E.ai
1)
Before starting operation, execute ‘Upload from device’, so that the “Device General Parameters” in the offline
database are synchronized with the device.
Upload data from the device does not include “User Flow Parameters”.*
*: “User Flow Parameters” consist of primary device information, fluid information and operating condition.
2)
Executing ‘Download to device’ will write both “Device Flow Parameters” and “Device General Parameters” into
the device. Before executing ‘Download to device’, execute ‘Upload from device’, so as to make “Device General
Parameters” in the offline database synchronized with the device.
Download data to device does not include “User Flow Parameters”.