<5. Operational Flowchart>

5-7

IM 01C25R51-01E

(A) New Configuration

Step

FieldMate Menu

DYF(SoftDL) F

OUNDATION

fieldbus DTM

Layer1

Layer2

Layer3

DYFMVTool

Main Window

Procedure

"Online Parameter" is opened.
Upload "Device Flow Parameters"

and "Device General Parameters".

Edit "Device General Parameters"

and Apply "Offline Database". 3)

"Initialize Menu" (If needed)

Initialize "User Flow Parameters"

and "Device Flow Parameters".

Select compensation and

edit "Device General Parameter".

Edit "User Flow Parameters".

Edit "User Flow Parameters".

Edit "User Flow Parameters" and

"Device Flow Parameters".

"Export -> Export VMV Menu"

Export "User Flow Parameters"

and "Device Flow Parameters" to

binary file.

Download

"Device Flow Parameters" and

"Device General Parameters".

Confirm the compensation

calculation by input simulation for

flow rate, temperature and

pressure.

"Report"

Export "User Flow Parameters" in

CSV file format.

Apply "Device Flow Parameters"

to "Offline Database".

Goes offline.

Save the "*.dns"

"User Flow Parameters", "Device

Flow Parameters" and "Device

General Parameters".

1

Start DTM and

upload

parameter

from the

device

Perform Flow

Configuration

Download

parameter to

the device

Confirm flow

configuration

Save settings

to DNS file

2

3

4

5

Device

Device

Parameter

Offline

Parameter

Flow

Configuration

Wizard

Flow

Configuration

Mode

Fluid Type

Setup

Fluid

Operating

Range Setup

Fluid Physical

Property

Setup

Apply Flow

Configuration

Assigned DTM

Device

Download to

device 2)

Upload from

device 1)

Parameter

Additional

Functions

Online

Parameter

Disconnect

Save to file...

Device

File

F0505E.ai

1)

Before starting operation, execute ‘Upload from device’, so that “Device General Parameters” of the flowmeter in

the offline database are synchronized with the device. Upload data from the device does not include “User Flow

Parameters”.

*: User Flow Parameters consist of fluid information and operating condition.

2)

Executing ‘Download to device’ will write both “Device Flow Parameters” and “Device General Parameters” into

the device. Before executing ‘Download to device’, execute ‘Upload from device’, so as to make “Device General

Parameters” of the flowmeter in the offline database synchronized with the device.

Download data to the device does not include “User Flow Parameters”.

3)

Temperature unit and pressure unit in AR Block are not configured in Flow Configurtion Wizard Detail Compensation

Mode.

These parameters must be set manually in AR Block offline parameter.