Modbus registers alphabetically, Modbus registers (alphabetical), Series f4p modbus registers – Watlow Series F4P User Manual

Page 96: Parameters sorted alphabetically

background image

901

°F or °C, System

r/w

0

°F

1

°C

103

% Power Output 1A, Status

r

Value

107

% Power Output 1B, Status

r

Value

3050

Activate Message, Digital Input 1

r/w

0

Message 1

1

Message 2

2

Message 3

3

Message 4

3051

Activate Message, Digital Input 2

r/w

0

Message 1

1

Messag

e 2

2

Message 3

3

Message 4

3052

Activate Message, Digital Input 3

r/w

0

Message 1

1

Message 2

2

Message 3

3

Message 4

3053

Activate Message, Digital Input 4

r/w

0

Message 1

1

Message 2

2

Message 3

3

Message 4

303

Alarm 1 High Deviation, Alarm Set Points

r/w

1 to 30000

303

Alarm 1 High Set Point, Alarm Set Points

r/w

to Alarm 1 Low Set Point

303

Alarm 1 Maximum High Rate, Alarm Set Points

r/w

Alarm 1 Low Maximum Rate +1 to 30000

302

Alarm 1 Low Deviation, Alarm Set Points

r/w

-19999 to -1

302

Alarm 1 Low Set Point, Alarm Set Points

r/w

to Alarm 1 High Set Point

302

Alarm 1 Maximum Low Rate, Alarm Set Points

r/w

-19999 to Alarm 1 Maximum Rate High -1

102

Alarm 1, Status

r

0

Off

1

Alarm High

2

Alarm Low

322

Alarm 2 High Deviation, Alarm Set Points

r/w

1 to 30000

322

Alarm 2 High Set Point, Alarm Set Points

r/w

to Alarm 2 Low Set Point

322

Alarm 2 Maximum High Rate, Alarm Set Points

r/w

Alarm 2 Low Maximum Rate +1 to 30000

321

Alarm 2 Low Deviation, Alarm Set Points

r/w

-9999 to -1

321

Alarm 2 Low Set Point, Alarm Set Points

r/w

to Alarm 2 High Set Point

321

Alarm 2 Maximum Low Rate, Alarm Set Points

r/w

-19999 to Alarm 2 Maximum Rate High -1

106

Alarm 2, Status

r

0

Off

1

Alarm High

2

Alarm Low

703

Alarm Hysteresis, Alarm Output 1

r/w

1 to 9999

720

Alarm Hysteresis, Alarm Output 2

r/w

1 to 9999

707

Alarm Logic, Alarm Output 1

r/w

0

Open on Alarm

1

Close on Alarm

724

Alarm Logic, Alarm Output 2

r/w

0

Open on Alarm

1

Close on Alarm

708

Alarm Messages, Alarm Output 1

r/w

0

Yes on Main Page

1

No

725

Alarm Messages, Alarm Output 2

r/w

0

Yes on Main Page

1

No

706

Alarm Sides, Alarm Output 1

r/w

0

Both

1

Low

2

High

723

Alarm Sides, Alarm Output 2

r/w

0

Both

1

Low

2

High

716

Alarm Source, Alarm Output 1

r/w

0

Input 1

1

Input 2

2

Input 3

733

Alarm Source, Alarm Output 2

r/w

0

Input 1

1

Input 2

2

Input 3

702

Alarm Type, Alarm Output 1

r/w

0

Off

1

Process

2

Deviation

3

Maximum Rate

719

Alarm Type, Alarm Output 2

r/w

0

Off

1

Process

2

Deviation

3

Maximum Rate

836

Analog Range, Retransmit Output 1

r/w

0

4 to 20mA

1

0 to 20mA

2

0 to 5V

3

1 to 5V

4

0 to 10V

837

Analog Range, Retransmit Output 2

r/w

0

4 to 20mA

1

0 to 20mA

2

0 to 5V

3

1 to 5V

4

0 to 10V

200

Auto/Manual Mode, Status

r/w

1

Auto Mode

2

Manual

1915

Auto/Manual Slidewire Calibration, Analog Input 3 r/w

r/w

0

Skip Calibration

1

Automatic

2

Manual

305

Autotune PID

r/w

0

Tune Off

9 . 2

C o m m u n i c a t i o n s

Wa t l o w S e r i e s F 4 P

Series F4P Modbus Registers

Parameters Sorted Alphabetically

A list of all Modbus registers in numerical order follows this alphabetical list. Register numbers listed are
relative. Add 40001 to convert to absolute addesses. For more information about parameters, see the Index.