Wa t l o w S e r i e s F 4 P

P a r a m e t e r s 6 . 1 1

Note: For more information about how parameter settings
affect the controller’s operation, see the Features Chapter.

Modbus

Register

Range

read/write

Conditions for

Parameter

Description

(Modbus Value)

Default

(I/O, Set)

Parameters to Appear

Active: Always.

880

r/w

Bumpless (0)

Bumpless Transfer (0)
Fixed (1)

Failure Mode

Select how the outputs
will behave if an input
error switches the con-
troller to manual mode.

Active: Always.

304

r/w

90% (90)

50 to 150%

(50 to 150)

Autotune Set Point

Set percent of set point
to auto-tune to.

Active: Always.

454

r/w

Restore Set

Point (0)

Restore Set Point (0)
Reverse Bumpless (1)

Manual to Auto Transfer

Select how the set point
will be determined when
control switches from
manual to auto mode.

Active if one or both control out-

puts is set to cool [direct].

453

r/w

-100.0%

(-1000)

-100.0% to 0.0%

(-1000 to 0) in tenths

Maximum Transfer Cool

The maximum cool out-
put power when control
is switched from auto to
manual mode.

Active if one or both control out-

puts is set to heat [reverse].

452

r/w

100.0%

(1000)

0.0% to 100.0%

(0 to 1000) in tenths

Maximum Transfer Heat

The maximum heat out-
put power when control
is switched from auto to
manual mode.

Active if input type is either RTD

or thermocouple.

1923 r/w

Yes, Upper

Display (1)

No, Upper Display (0)
Yes, Upper Display (1)

Show °F or °C

Choose whether to dis-
play or hide °C or °F in
top display.

Active: Always.

901

r/w

°F (0)

°F (0)
°C (1)

°F or °C

Choose temperature
scale.

Active: Always.

900

r/w

US (0)

US (US will be in

Reset/Rate) (0)

SI (SI will be in Inte-

gral/Derivative) (1)

PID Units

Choose units for PID
control.

Main > Setup >

System

System

Setup Page Parameters