beautypg.com

Factory page parameter table, Diagnostic – Watlow Series F4P User Manual

Page 53

background image

Wa t l o w S e r i e s F 4 P

P a r a m e t e r s

6 . 2 7

Note: For more information about how parameter settings affect the
controller’s operation, see the Features Chapter.

Factory Page Parameter Table

Modbus

Register

Range

read/write

Conditions for

Parameter

Description

(Modbus Value)

Default

(I/O, Set)

Parameters to Appear

Active: Always.

8 r

Univ Single (7)

Input 1

Displays the input 1
type.

Active: Always.

4 r

0.00 to 9.99
(0 to 999)

Software Revision

Identifies the software
revision.

Active: Always.

3 r

00 to 99
(0 to 99)

Software Number

Identifies the software
ID number.

Active: Always.

1 [1st part]
2 [2nd

part]

r

000000 to 999999

(0 to 999999)

Serial Number

Identifies the individual
controller.

Active: Always.

5 r

0100 to 5200

(0100 to 5200)

Manufactured Date

Identifies the manufac-
ture date.
(WWYY) Week:Year

Active: Always.

0 r

P4
(4P) ASCII

5280 Dec

P4
(4P) ASCII 5280 Dec

Model

First Digits

Main > Factory >

Diagnostic

Diagnostic

Available if Control Type (Setup

Page > Analog Input 2 or 3) is
set to Remote.

1319 r/w

Full Access

(0)

Full Access (0)
Read Only (1)
Password (2)
Hidden (3)

Operations, Remote/Local

Set Point
Set access to the Re-
mote/Local Set Point.

Active if any Digital Input is set

to Digital Set Point.

1318 r/w

Full Access

(0)

Full Access (0)
Read Only (1)
Password (2)
Hidden (3)

Operations, Control Set

Point
Set access to the Control
Set Point.

Active: Always.

1317 r/w

Full Access

(0)

Full Access (0)
Read Only (1)
Password (2)
Hidden (3)

Operations, Ramp Set Point

Set access to the Ramp
Set Point.

Active: Always.

1316 r/w

Full Access

(0)

Full Access (0)
Read Only (1)
Password (2)
Hidden (3)

Operations, PID Crossover

Set access to PID
Crossover.