Operations page parameter table, Control set points – Watlow Series F4P User Manual

Page 34

background image

6 . 8

P a r a m e t e r s

Wa t l o w S e r i e s F 4 P

Note: Press the Information Key

ˆ for more task-related tips.

Operations Page Parameter Table

Modbus

Register

Range

read/write

Conditions for

Parameter

Description

(Modbus Value)

Default

(I/O, Set)

Parameters to Appear

Active if any digital input is set

to Digital Set Point.

308

[1]

327

[2]

346

[3]

365

[4]

r/w

Set Point Low Limit to

Set Point High Limit

Digital Set Point x (1 to 4)

Select the set point
value that will be acti-
vated by digital input x.
The set point name can
be changed in the Setup
Page.

Active if Boost Type (Setup Page

> Control Output 1B) is set to
Boost On Set Point. Based on
decimal setting.

309

r/w

cool/cool
Set Point

High Limit
(process)

999 (dev.)
heat/heat
Set Point

Low Limit
(process)

-999 (dev.)

-19999 to 30000
-1999.9 to 3000.0
-199.99 to 300.00
-19.999 to 30.000
Set Point Low Limit to

Set Point High Limit
[process]

(-19999 to 30000) in in-

teger, tenths, hun-
dredths or thou-
sandths

Boost Set Point (1B)

Set the set point that
will control output 1B.

Active if Boost Type (Setup Page

> Control Output 1B) is set to
Boost On Power.

884

r/w

0

0 to 999 seconds

(0 to 999)

Boost Delay Time (1B)

Set the time that the
power level has to be ex-
ceeded before activating
output 1B.

Active if Boost Type (Setup Page

> Control Output 1B) is set to
Boost On Power.

883 r/w

75%

0.0% to 100.0%

(0 to 1000)

Boost Power (1B)

Select the minimum out-
put 1A power that will
activate output 1B (with
1.0% hysteresis).

Main > Operations >

Control Set Points

Control Set Points

Active if Ramp to Set Point Mode

is not set to Off.

1101 r/w

100.0

1 to 999
1 to 99.9
1 to 9.99
1 to 0.999
(1 to 999) in integer,

tenths, hundredths or
thousandths

Ramp to Set Point Rate

Select the maximum
rate of temperature or
process value change.

Active if Ramp to Set Point Mode

is not set to Off.

1102 r/w

Degrees/

Minute

Degrees/Minute (0)
Degrees/Hour (1)

Ramp to Set Point Scale

Select the units of mea-
sure for ramping.