beautypg.com

Differential control, Ratio control – Watlow Series F4P User Manual

Page 75

background image

Wa t l o w S e r i e s F 4 P

F e a t u r e s

7 . 1 7

Differential Control

The Series F4P with the enhanced control option can be
configured to support differential control. Differential
control allows the Series F4P to control one process at a
difference to another process.

Analog input 3 is configured as the differential input.
The process value measured on input 3 is added to the
differential value [Set Diff.] to become the closed-loop
control set point [CTL SP]. Four additional differential

values (Dgt. Diff. Value) can be enabled remotely through
designated digital inputs. The nameable digital differen-
tial values are entered in the Operations Menu > Control
Set Points.

Differential control is only available in enhanced control
operation. Changes to the differential value or Analog In-
put 3 during auto-tune are not acted on until the auto-
tune process is completed or aborted.

Location in software: Setup Page > Analog Input 3 and
Setup Page > Digital Input x (1 to 4).

Ratio Control

The Series F4P with the enhanced control option can be
configured to support ratio control, which is especially
useful in applications that mix materials.

Analog input 3 is configured as the ratio input. The pro-
cess value measured on input 3 multiplied by the ratio
value [Set Ratio] becomes the closed loop control set
point [CTL SP]. Four additional ratio values (Dgt. Ratio
Value) can be enabled remotely through designated digi-

tal inputs. The nameable digital ratio values are entered
in the Operations Menu > Control Set Points.

Ratio control is only available in enhanced control opera-
tion. Changes to the ratio value or analog input 3 during
auto-tune are not acted on until the auto-tune process is
completed.

Location in software: Setup Page > Analog Input 3 and

Setup Page > Digital Input x (1 to 4).

Figure 7.17a — Differential Control Application Example.

Figure 7.17b — Ratio Control Application Example.

input 1

input 3

output 1

controlled flow
of pigment

flow

transmitter

motorized
valve

Mixing Tank

flow

transmitter

mixed paint

uncontrolled
flow of
unmixed paint

F

4

1

2

1B

1B

1A

1A

A

M

/