beautypg.com

Watlow Series F4P User Manual

Page 104

background image

1923

Show °F or °C, System

r/w

0

No, Upper Display

1

Yes, Upper Display

313

Silence Alarm 1, Key Press Simulation

w

0 to 9999

332

Silence Alarm 2, Key Press Simulation

w

0 to 9999

705

Silencing, Alarm Output 1

r/w

0

No

1

Yes

722

Silencing, Alarm Output 2

r/w

0

No

1

Yes

1916

Slidewire Deadband, Analog Input 3

r/w

3 to 1000% (in tenths)

1917

Slidewire Hysteresis, Analog Input 3

r/w

0 to 1000% (in tenths)

1918

Slidewire Learn Closed, Analog Input 3

r/w

(Close the valve manually.)

1919

Slidewire Learn Open, Analog Input 3

r/w

(Open the valve manually.)

3

Software Number, Diagnostic

r

00 to 99

5569

Square Root, Analog Input 1

r/w

0

Off

1

On

5570

Square Root, Analog Input 2

r/w

0

Off

1

On

5571

Square Root, Analog Input 3

r/w

0

Off

1

On

1514

Test Outputs, Test

w

0

All Off

1

Output 1A

2

Output 1B

5

Retransmit 1

6

Retransmit 2

7

Alarm 1

8

Alarm 2

9

All On

10 Communications

601

Sensor Type, Analog Input 1

r/w

0

J

1

K

2

T

3

E

4

N

5

C

6

D

7

PT2

8

R

9

S

10 B
11 DIN 100

RTD

12 JIS 100

RTD

13 4 to 20mA
14 0 to 20mA
15 0 to 5V
16 1 to 5V
17 0 to 10V
18 0 to 50mV
23 DIN 500

RTD

24 JIS 500

RTD

25 DIN 1k

RTD

26 JIS 1k

RTD

611

Sensor Type, Analog Input 2

r/w

0

J

1

K

2

T

3

E

4

N

5

C

6

D

7

PT2

8

R

9

S

10 B
11 DIN 100

RTD

12 JIS 100

RTD

13 4 to 20mA
14 0 to 20mA
15 0 to 5V
16 1 to 5V
17 0 to 10V
18 0 to 50mV
23 DIN 500

RTD

24 JIS 500

RTD

25 DIN 1k

RTD

26 JIS 1k

RTD

621

Sensor Type, Analog Input 3

r/w

0

J

1

K

2

T

3

E

4

N

5

C

6

D

7

PT2

8

R

9

S

10 B
11 DIN 100

RTD

12 JIS 100

RTD

13 4 to 20mA
14 0 to 20mA
15 0 to 5V
16 1 to 5V
17 0 to 10V
18 0 to 50mV
19 Slidewire
23 DIN 500

RTD

24 JIS 500

RTD

25 DIN 1k

RTD

26 JIS 1k

RTD

3070-72

Units (Char 1-3), Analog Input 1

r/w

ASCII codes 0-9, A-Z, space

3073-75

Units (Char 1-3), Analog Input 2

r/w

ASCII codes 0-9, A-Z, space

3076-78

Units (Char 1-3), Analog Input 3

r/w

ASCII codes 0-9, A-Z, space

608

Units, Analog Input 1

r/w

0

Temperature

1

Units [3 characters]

618

Units, Analog Input 2

r/w

0

Temperature

1

Units [3 characters]

628

Units, Analog Input 3

r/w

0

Temperature

1

Units [3 characters]

9 . 1 0

C o m m u n i c a t i o n s

Wa t l o w S e r i e s F 4 P