Watlow Series F4P User Manual

Page 100

background image

6

Digital Set Point

7

Differential Set Point

8

Digital Ratio

9

Remote 2

10 Remote 3
11 Alternate Control
12 Manual Control
13 Reverse Outputs
14 Activate Messages
15 Lock Auto/Man

1066

Function, Digital Input 4

r/w

0

Off

1

Panel Lock

2

Reset Alarm 1

3

Reset Alarm 2

4

Reset Both Alarms

5

Control Outputs Off

6

Digital Set Point

7

Differential Set Point

8

Digital Ratio

9

Remote 2

10 Remote 3
11 Alternate Control
12 Manual Control
13 Reverse Outputs
14 Activate Messages
15 Lock Auto/Man

714

High Power Limit, Control Output 1A

r/w

Low Limit+1 to 100%

731

High Power Limit, Control Output 1B

r/w

Low Limit+1 to 100%

711

High Scale, Retransmit Output 1

r/w

-19999 to 30000 (maximum sensor range)

728

High Scale, Retransmit Output 2

r/w

-19999 to 30000 (maximum sensor range)

2607

Hysteresis 1A, Cascade PID Set 1

r/w

1 to 30000

2627

Hysteresis 1A, Cascade PID Set 2

r/w

1 to 30000

2647

Hysteresis 1A, Cascade PID Set 3

r/w

1 to 30000

2667

Hysteresis 1A, Cascade PID Set 4

r/w

1 to 30000

2687

Hysteresis 1A, Cascade PID Set 5

r/w

1 to 30000

507

Hysteresis 1A, PID Set 1

r/w

1 to 30000

517

Hysteresis 1A, PID Set 2

r/w

1 to 30000

527

Hysteresis 1A, PID Set 3

r/w

1 to 30000

537

Hysteresis 1A, PID Set 4

r/w

1 to 30000

547

Hysteresis 1A, PID Set 5

r/w

1 to 30000

2617

Hysteresis 1B, Cascade PID Set 1

r/w

1 to 30000

2637

Hysteresis 1B, Cascade PID Set 2

r/w

1 to 30000

2657

Hysteresis 1B, Cascade PID Set 3

r/w

1 to 30000

2677

Hysteresis 1B, Cascade PID Set 4

r/w

1 to 30000

2697

Hysteresis 1B, Cascade PID Set 5

r/w

1 to 30000

557

Hysteresis 1B, PID Set 1

r/w

1 to 30000

567

Hysteresis 1B, PID Set 2

r/w

1 to 30000

577

Hysteresis 1B, PID Set 3

r/w

1 to 30000

587

Hysteresis 1B, PID Set 4

r/w

1 to 30000

597

Hysteresis 1B, PID Set 5

r/w

1 to 30000

1504

Input 1 AtoD, Diagnostic

r

HHHH

101

Input 1 Error, Status

r

0

None

1

AtoD Under Flow

2

Sensor Under Range

3

Sensor Over Range

4

AtoD Over Flow

5

AtoD Timeout

6

Open Loop

903

Input 1 Failure, System

r/w

0% to High Power Limit (heat only or cool only)
Cool High Power Limit to Heat High Power Limit
(heat/cool or cool/heat)

210

Input 1 Open Loop, Status

r

(0) Off, (1) On

100

Input 1 Value, Status

r

xx

8

Input 1, Diagnostic

r

0

None

8

Univ

1505

Input 2 AtoD, Diagnostic

r

HHHH

9

Input 2, Diagnostic

r

0

None

8

Univ

1506

Input 3 AtoD, Diagnostic

r

HHHH

10

Input 3, Diagnostic

r

Univ

2601

Integral 1A, Cascade PID Set 1

r/w

0 to 9999 minutes in hundredths

2621

Integral 1A, Cascade PID Set 2

r/w

0 to 9999 minutes in hundredths

2641

Integral 1A, Cascade PID Set 3

r/w

0 to 9999 minutes in hundredths

2661

Integral 1A, Cascade PID Set 4

r/w

0 to 9999 minutes in hundredths

2681

Integral 1A, Cascade PID Set 5

r/w

0 to 9999 minutes in hundredths

501

Integral 1A, PID Set 1

r/w

0 to 9999 minutes in hundredths

511

Integral 1A, PID Set 2

r/w

0 to 9999 minutes in hundredths

521

Integral 1A, PID Set 3

r/w

0 to 9999 minutes in hundredths

531

Integral 1A, PID Set 4

r/w

0 to 9999 minutes in hundredths

541

Integral 1A, PID Set 5

r/w

0 to 9999 minutes in hundredths

2611

Integral 1B, Cascade PID Set 1

r/w

0 to 9999 minutes in hundredths

2631

Integral 1B, Cascade PID Set 2

r/w

0 to 9999 minutes in hundredths

2651

Integral 1B, Cascade PID Set 3

r/w

0 to 9999 minutes in hundredths

2671

Integral 1B, Cascade PID Set 4

r/w

0 to 9999 minutes in hundredths

2691

Integral 1B, Cascade PID Set 5

r/w

0 to 9999 minutes in hundredths

551

Integral 1B, PID Set 1

r/w

0 to 9999 minutes in hundredths

561

Integral 1B, PID Set 2

r/w

0 to 9999 minutes in hundredths

571

Integral 1B, PID Set 3

r/w

0 to 9999 minutes in hundredths

9 . 6

C o m m u n i c a t i o n s

Wa t l o w S e r i e s F 4 P