4. Operation Using I/O Signals

4.3.3

Timings after Power On

z Steps from Initial Startup to Actuator Adjustment

[1] Confirm that the slider or rod is not contacting a mechanical end or that the work is not contacting any

peripheral equipment.

[2] Cancel the emergency stop or connect the motor drive power.
[3] Supply the 24-VDC I/O power: PIO connector pins 1 and 2.
[4] Supply the 24-VDC controller power: 24-V and 0-V terminals on the power-supply terminal block.
[5] Set the minimum required parameters. Refer to 4.2.2, “Setting Parameters Required for Operation.”

Reference To temporarily disable the servo-on input because the PLC is not yet ready to accept the input,

change the value of Parameter No. 21 (Servo-on input disable selection) to “1.”

[6] Input a servo-on signal from the PLC (if the servo-on input is enabled).
[7] Input a homing signal from the PLC.
[8] Input position command pulses from the PLC.

Safety circuit status

Supply of 24-VDC I/O
power

Supply of 24-VDC
controller power

Servo-on input (SON)

SV lamp (front panel)

Homing input
(HOME)

Homing complete
output (HEND)

Command pulse input

Emergency stop cancelled

An orange light
comes on for 2
seconds, and
then turns off.

Green

Min. 170 msec

Min. 6 msec

T

1

(Note1: Next page)