beautypg.com

4 heat radiation and installation – IAI America PCON-PO User Manual

Page 33

background image

21

3. Installation and W

iring

3.4

Heat Radiation and Installation

Design the control panel size, controller layout and cooling method so that the temperatures around the controller will
always be kept to 40?C or below.
Mount the controller vertically on the wall, as shown below. Since cooling is provided by means of natural convection,
follow this orientation and provide a minimum clearance of 50 mm above and below the controller to allow sufficient
airflows to circulate.
If you are installing multiple controllers side by side, provide a fan on top of the controllers to agitate the airflows as
an effective way to keep the surrounding temperatures constant.
Provide a minimum clearance of 80 mm between the front face of the controller and the wall (cover).

Regardless of whether you are installing one or more controllers, provide sufficient clearances around each controller
to permit easy access for installation and removal of the controller.

Fan

At least 50 mm

At least 50 mm

At least 80 mm

Airflow