3 push type, 1 explanation of i/o signals – IAI America PCON-PO User Manual
Page 60
48
4. Operation Using I/O Signals
4.3 Push
Type
Use the PIO pattern of this type if you wish to perform position control and push-motion operation using pulse train
input from a PLC.
Set User Parameter No. 25 (PIO pattern selection) to “1.”
4.3.1
Explanation of I/O Signals
Pin No.
Signal
Name
Remarks
1
24 V
External 24 V
2
0 V
External ground
If the controller is used in the open collector mode, also use this
pin for the COMMON signal for command pulses as well as the
0V signal for the controller’s control power.
3 IN0
SON
Servo-on
signal
4
IN1
TL
Torque-limit selection signal
5 IN2
HOME
Homing
signal
6 IN3
RES
Reset
signal/deviation-counter clear signal
7 OUT0
SV
Servo-on
output
8
OUT1
INP
Positioning complete signal/torque limit signal
9
OUT2
HEND
Homing complete signal
10 OUT3
*ALM
Alarm
signal
11 /PP
Command
pulse
12 PP
Command
pulse
Not connected if the controller is used in the open collector
mode.
13 /NP
Command
pulse
14 NP
Command
pulse
Not connected if the controller is used in the open collector
mode.
Servo-on Command Input (SON)
The servo remains on while this signal is ON.
The actuator can be operated while the SON signal is ON.
While this signal is OFF, the actuator does not operate even when the controller power is supplied.
If the SON signal is turned OFF while the actuator is operating, the actuator will decelerate at the forced-stop torque
until it stops. After the actuator stops, the servo will turn off and the motor will enter a free-run state.
If the actuator is equipped with a brake, the function specified by the applicable parameter (electromagnetic brake)
is activated.
When the servo turns off, the deviation counter will be cleared (if User Parameter No. 58 Clear deviation at servo
off/alarm stop is set to “Enable.”)
Reset Signal Input (RES)
This signal resets the alarms currently detected by the controller.
You can turn the RES signal ON to reset the alarms currently detected by the controller.
Caution:
This signal cannot reset cold-start level alarms. Identify the cause of each alarm and remove the
cause before restarting the controller.
Deviation-counter Clear Signal (DCLR)
While the TL signal is ON, the RES signal functions as the deviation-counter clear signal (DCLR).
The deviation counter is cleared continuously while this signal is ON.
Upon completion of push-motion operation, you can clear the deviation counter by inputting this signal.