S/hart) – Burkert Type 8635 User Manual
Page 96

94 - 8635
O
PERATING THE
P
ROCESS
C
ONTROLLER
(S/HART)
P.CO - PARA
Parameters of the PID process controller
Amplification factor of the process controller
0 ... 99.99 (factory setting 1.00)
Operating point
0.0 ... 100 % (factory setting 0 %)
Rate time
0 s ... 999.9 s (factory setting 0 s)
Reset time
0.5 s ... 999.9 s (factory setting 999.9 s)
NOTE
The parameters that were entered should be noted in the table in Appendix
Tables for
process controller.
For definition of the parameters of a PID controller, see Appendix
General Rules.
For self-parametrization of the PID parameters, see step
.
P.CO - SETP
Type of setpoint setting (internal / external)
Setpoint setting internally via the keys on the SIDE
Control
(S/HART).
Setpoint setting externally via the standard signal
input.
P.CO SETP
SETP INT
SETP EXT
P.CO PARA
KP XX.XX
TN XXX.X
TV XXX.X
XO XXX
- Type 0125 (15 pages)
- Type 0121 (4 pages)
- Type 0330 (2 pages)
- Type 0331 (4 pages)
- Type 6012 (4 pages)
- Type 0127 (18 pages)
- Type 0131 (5 pages)
- Type 0141 (5 pages)
- Type 0142 (12 pages)
- Type 0145 (3 pages)
- Type 0174 (5 pages)
- Type 0212 (2 pages)
- Type 0211 (5 pages)
- Type 0212-B (18 pages)
- Type 0250 (64 pages)
- Type 0253 (2 pages)
- Type 0255 (15 pages)
- Type 0355 (2 pages)
- Type 0255 (2 pages)
- Type 8006 (34 pages)
- Type 8640 (2 pages)
- Type 8640 (55 pages)
- Type 8640 (119 pages)
- Type 0256 (15 pages)
- Type 0256 (2 pages)
- Type 0258 (72 pages)
- Type 0262 (5 pages)
- Type 0273 (6 pages)
- Type 0280 (5 pages)
- Type 0280 (2 pages)
- Type 0280 (12 pages)
- Type 0281 (2 pages)
- Type 0282 (2 pages)
- Type 0283 (2 pages)
- Type 0286 (4 pages)
- Type 0287 (15 pages)
- Type 0290 (2 pages)
- Type 0290 (14 pages)
- Type 0293 (18 pages)
- Type 0300 (6 pages)
- Type 0301 (6 pages)
- Type 0311 (2 pages)
- Type 0312 (6 pages)
- Type 6519 (3 pages)
- Type 6519 (4 pages)