8635 - 55
O
PERATING AND
C
ONTROLLER
F
UNCTIONS
ADDFUNCT
see section
Configuring the supplementary functions.
➔ Jump over this menu item on first commissioning.
X.TUNE
- AUTOTUNE for positioners
Start the automatic adaptation of the positioner to the current operating
conditions (X.TUNE)
The following functions are initiated automatically:
• Adaptation of the sensor signal to the (physical) stroke of the valve used.
• Determination of parameters for driving the integral piezoelectric positioning system
• Setting of the controller parameters of the positioner.
Optimization is done according to the criteria: as short a correcting time as possible and freedom
from overshoot.
END
EEPROM
ADDFUNCT
X.TUNE
X.TUNE END
5 s
5 s
Operating mode
or
AUTOMATIC
MANUAL
Main menu for settings on commissioning
Description of procedure
- Type 0125 (15 pages)
- Type 0121 (4 pages)
- Type 0331 (4 pages)
- Type 6012 (4 pages)
- Type 0330 (2 pages)
- Type 0127 (18 pages)
- Type 0131 (5 pages)
- Type 0141 (5 pages)
- Type 0142 (12 pages)
- Type 0145 (3 pages)
- Type 0174 (5 pages)
- Type 0212 (2 pages)
- Type 0211 (5 pages)
- Type 0212-B (18 pages)
- Type 0250 (64 pages)
- Type 0253 (2 pages)
- Type 0255 (15 pages)
- Type 0355 (2 pages)
- Type 0255 (2 pages)
- Type 8006 (34 pages)
- Type 8640 (2 pages)
- Type 8640 (55 pages)
- Type 8640 (119 pages)
- Type 0256 (15 pages)
- Type 0256 (2 pages)
- Type 0258 (72 pages)
- Type 0262 (5 pages)
- Type 0273 (6 pages)
- Type 0280 (2 pages)
- Type 0280 (12 pages)
- Type 0280 (5 pages)
- Type 0281 (2 pages)
- Type 0282 (2 pages)
- Type 0283 (2 pages)
- Type 0286 (4 pages)
- Type 0287 (15 pages)
- Type 0290 (2 pages)
- Type 0290 (14 pages)
- Type 0293 (18 pages)
- Type 0300 (6 pages)
- Type 0301 (6 pages)
- Type 0312 (6 pages)
- Type 0311 (2 pages)
- Type 6519 (3 pages)
- Type 6519 (4 pages)