Profibus pa) – Burkert Type 8635 User Manual
Page 119
8635 - 117
C
ONFIGURATION FOR
B
US
C
OMMUNICATION
(PROFIBUS PA)
* not available via PDM or Commuwin
N: Non-volatile parameter
S: Static revision counter parameter
D: Dynamic parameter
C: Constant parameter
SETP_DEVIATION_LIMIT
0: function switched off,
otherwise limit value (7) of setpoint. On exceeding, 0 x 02 is outputted in the 1st byte of the diagnosis
extension and a diagnosis message generated.
TIME_OUT_MONITOR
A time (100 ms basis) is started when the setpoint leaves the dead band. If this time exceeds the limit,
0 x 01 is outputted in the 1st byte of the diagnosis extension and a diagnosis message generated.
The bit remains in place for 10 s.
Parameter
Slot
index
Index
abso-
lute
Read
Write
Type
Size
byte
Memory
class
Transducer Block (Analog Output)
VALVE_MAINT_DATE
1
151
X
X
OSTRING
16
S
SERVO_GAIN_2
1
152
X
X
FLOAT
4
S
TAB_OP_CODE
1
155
X
X
UNSIGNED8
1
D
TAB_STATUS
1
156
X
UNSIGNED8
1
D
POSITIONING_VALUE
1
157
X
DS-33
5
D
FEEDBACK_VALUE
1
158
X
DS-33
5
D
VALVE_MAN
1
159
X
X
OSTRING
16
S
ACTUATOR_MAN
1
160
X
X
OSTRING
16
S
VALVE_TYP
1
161
X
X
OSTRING
1
S
ACTUATOR_TYPE
1
162
X
UNSIGNED8
1
C
ACTUATOR_ACTION
1
163
X
X
UNSIGNED8
1
S
VALVE_SER_NUM
1
164
X
X
OSTRING
16
S
ACTUATOR_SER_NUM
1
165
X
X
OSTRING
16
S
ADD_GEAR_SER_NUM
1
166
X
X
OSTRING
16
S
ADD_GEAR_MAN
1
167
X
X
OSTRING
16
S
ADD_GEAR_ID
1
168
X
X
OSTRING
16
S
ADD_GEAR_INST_DATE
1
169
X
X
OSTRING
16
S
*SETP_DEVIATION_LIMIT
1
180
X
X
FLOAT
4
S
*TIME_OUT_MONITOR_VALUE
1
181
X
X
UNSIGNED16 2
D
*TIME_OUT_MONITOR_LIMIT
1
182
X
X
UNSIGNED16 2
S
View
1
200
X
OSTRING
13
D