S/hart) – Burkert Type 8635 User Manual
Page 27
8635 - 25
S
YSTEM
D
ESCRIPTION
(S/HART)
Analog repeat (optional)
4 ... 20 mA (electrically isolated)
Supply voltage
U
supply
= 12 ... 30 V DC
Burden
U
supply
≥ 12 V + RB • 20 mA
Binary outputs (optional)
to EN 50 227 (electrically isolated)
Supply voltage
5 ... 11 V DC
Current in switching status OPEN < 1.2 mA
Current in switch. status CLOSE
> 2.1 mA
Sense of action
NO (normally open) or NC (normally closed)
(may be parametrized)
max. permissible values
see Declaration of Conformity
PNEUMATIC DATA
Control medium
Quality classes to DIN ISO 8573-1
Dust content
Class 5:
max. 40 µm particle size
max. 10 mg/m³ particle density
Water content
Class 3:
max. pressure dew point
- 20 °C or at least 10 degrees below lowest
operating temperature
Oil content
Class 3: max. 1 mg/m³
Temperatur range of
- 25 ... + 65 °C (with non-Ex devices or T4/T5)
compressed air
- 25 ... + 60 °C (with T6)
Pressure range
1.4 ... 6.0 bar
Supply pressure
variation
max. ± 10 % during operation
Air flow capacity of control valve
at 1.4 bar pressure drop
over valve
ca. 55 L
N
/min STP for pressurizing and exhausting
at 6 bar pressure drop
over valve
ca. 170 L
N
/min STP for pressurizing and exhausting
Self-consumption of air
in balanced state
0.0 L
N
/min STP
Throttle screw
adjustment ratio ca.10:1
Connections
G1/4'' internal thread