S/hart) – Burkert Type 8635 User Manual
Page 104

102 - 8635
O
PERATING THE
P
ROCESS
C
ONTROLLER
(S/HART)
Step
- Process tune ready to start
You are in the
process operating level in the AUTOMATIC mode.
Make ready process tune by the following operating procedure:
The next setpoint step entered via the keypad (see Step ) is now used for parameter optimization.
The setpoint
SP is set equal to the actual sensor value PV and is the starting value for the optimization
step.
Adaptation / modification of this starting value is described in Step .
Readiness of process tune is symbolized in the display by three horizontal bars behind the flashing
setpoint symbol
SP .
Step
- Adaptation of the starting value for the optimization step (optional)
If required you can carry out an adaptation of the starting value for the optimization step. Switch the
device to the
MANUAL mode. By pressing the arrow keys, open or close the process valve, which
causes a corresponding change in the process value
PV. As soon as the desired starting value is set,
switch the device back to the
AUTOMATIC mode.
Step
- Initiate process tune
You are in the process operating level in the
AUTOMATIC mode.
Process tune is now initiated by entering via the keypad a setpoint step. This step should take place in
the future working range of the process control system.
The procedure is as follows:
With the display
SP (setpoint) set, press one of the arrow keys for longer than 3
seconds to activate the mode for changing the process setpoint. After release of the
key, the first digit of the process setpoint flashes.
Set the value of the flashing digit of the process setpoint
SP.
Confirm the value set and move to the next digit. After confirmation of the fourth
digit, the process setpoint set is stored as the end value of the process setpoint
step.
or
or
> 3 s
Make ready
P.TUNE
(process tune)
process tune
ready
process tune
not ready
and